Knightsbridge TNXQUADSTW Installation & Maintenance Manual

Advertisement

INSTALLATION & MAINTENANCE MANUAL
TNXQUADSTW / TNXQUADSTBK
TNXONESTW / TNXONESTBK

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TNXQUADSTW and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Knightsbridge TNXQUADSTW

  • Page 1 INSTALLATION & MAINTENANCE MANUAL TNXQUADSTW / TNXQUADSTBK TNXONESTW / TNXONESTBK...
  • Page 2: General Instructions

    These instructions should be used to aid installation of the following products: TNXQUADSTW / TNXQUADSTBK / TNXONESTW / TNXONESTBK SAFETY • This product must be installed in accordance with the latest edition of the IEE Wiring Regulations (BS7671) and current Building Regulations.
  • Page 3 surface using the plugs and screws provided manufacturer of the sensors that they are compatible with LED luminaires. Ensuring correct polarity is observed, carefully wire as shown in Fig. 1 • Provide power to the required point of installation (refer to BS7671 for correct cabling methods). •...
  • Page 4: Self-Test Function

    Fig. 3 • Re-attach the diffuser to the luminaire body using the four screws • Switch on and check for correct operation ensuring the green indicator LED is illuminated Fig. 3 • See below for operation of the self-test function •...
  • Page 5 LED INDICATOR STATUS Solid green Normal conditions, battery is charged / charging Slow flash green (1 sec on, 1 sec off) Self-test (function or duration test) underway Solid red Battery fault Slow flash red (1 sec on, 1 sec off) Lamp fault Fast flash red (0.25 sec on, 0.25 sec off) Failed duration test...
  • Page 6: Warranty

    Clean with a soft dry cloth only, do not use aggressive cleaning products or solvents which may damage the product. Do not use any source of high-pressure washers to maintain or clean this luminaire. This product is non-dimmable. This product should be dismantled for disposal when it reaches the end of its life. Please see website for dismantling instructions.
  • Page 7 Alternatively, simulate a mains supply failure for 3-hour continuous test by operation of key switch, or switching off circuit breaker. Ensure normal supply is restored after test and check status of bi-colour LED indicator • If the luminaire fails any of the above tests, please contact a qualified electrician. Results should be recorded, even when obtained via the self-test function.
  • Page 8 230V IP65 50Hz °C SUPPLIED BY: (UK) MANUFACTURER (EU) AUTHORISED REPRESENTATIVE ML ACCESSORIES LTD, SLV LIGHTING GROUP, UNIT E CHILTERN PARK, DAIMLERSTRASSE 21-23, BOSCOMBE ROAD, DUNSTABLE 52531 ÜBACH-PALENBERG, GERMANY LU5 4LT, EMAIL: EPREL@GROUP.SLV.COM WWW.MLACCESSORIES.CO.UK AKDEC22_V1 MADE IN CHINA...

This manual is also suitable for:

TnxquadstbkTnxonestwTnxonestbkTnxtst