7.3.1

Device configuration dialog

Dialog with device-specific settings.
Setting or
Value range
function
Battery Type
C9900-U330,
(combo box)
C9900-U332,
User-Defined
Battery Type
0..99
(edit field)
Nominal
0..99900 [mAh]
Battery
Capacity
Internal
0..999 [mOhm]
Battery
Resistance
Battery
0..480 [months]
replace
service
interval
CU8110-0060
Default value
Description
C9900-U330
Configures the used Beckhoff battery pack type.
1
Available only if "User-Defined" battery type is selected.
The setting is necessary, for instance, to be able to
calculate the remaining charge available under battery
operation.
3400
Available only if "User-Defined" battery type is
selected.The setting is necessary, for instance, to be able
to calculate the remaining charge available under battery
operation.
120
Available only if "User-Defined" battery type is
selected.The setting is necessary, for instance, to be able
to calculate the remaining charge available under battery
operation.
60 (5 years)
The user is able to enter/configure the battery replace
service interval (number of months) before first warning is
and checkbox
logged to Windows eventlog.
not enabled
Use the checkbox to activate or deactivate the
functionality. The functionality is only available if the
battery change date and system time (in the task bar) is
also set/configured.
The UPS service compares the configured battery
change date to the configured service interval at service
start. If battery replace date + service interval >= current
system date => Windows Eventlog warning message will
be logged.
The warning message do not reflects the real battery
condition and can be used as reminder to check the real
battery condition or battery age.