Manual | EN
CU8110-0060
Uninterruptible Power Supply (Capacitive)
2024-01-23 | Version: 1.0

Advertisement

Table of Contents
loading

Summary of Contents for Beckhoff CU8110-0060

  • Page 1 Manual | EN CU8110-0060 Uninterruptible Power Supply (Capacitive) 2024-01-23 | Version: 1.0...
  • Page 3: Table Of Contents

    TwinCAT interface...........................  38 7.5.1 FB_GetUPSStatus ...................... 38 7.5.2 ST_UPSStatus .........................  40 7.5.3 E_BatteryStatus .......................  43 7.5.4 E_UpsCommStatus...................... 43 7.5.5 E_UpsPowerStatus ...................... 44 8 Error handling and diagnostics ...................... 45 9 Care and maintenance .......................... 46 10 Decommissioning ...........................  47 CU8110-0060 Version: 1.0...
  • Page 4 Table of contents 10.1 Dismantling the UPS ........................ 47 10.2 Disposal ............................ 48 11 Technical data ............................ 49 12 Appendix .............................. 51 12.1 Accessories .............................  51 12.2 Support and Service........................ 52 Version: 1.0 CU8110-0060...
  • Page 5: Notes On The Documentation

    EP1590927, EP1789857, EP1456722, EP2137893, DE102015105702 and similar applications and registrations in several other countries. ® EtherCAT is registered trademark and patented technology, licensed by Beckhoff Automation GmbH, Germany Copyright © Beckhoff Automation GmbH & Co. KG, Germany. The distribution and reproduction of this document, as well as the use and communication of its contents without express authorization, are prohibited.
  • Page 6: Representation And Structure Of Warnings

    There is a potential hazard to the environment and equipment. Notes showing further information or tips: This notice provides important information that will be of assistance in dealing with the product or software. There is no immediate danger to product, people or environment. Version: 1.0 CU8110-0060...
  • Page 7: Documentation Issue Status

    Notes on the documentation Documentation issue status Version Modifications First version. CU8110-0060 Version: 1.0...
  • Page 8: Safety

    Intended use The CU8110-0060 UPS is intended for mounting on a DIN rail in an industrial control cabinet or terminal box. Alternatively, the UPS can be equipped with a mounting plate and mounted on the rear panel of the control cabinet.
  • Page 9 • During firefighting wear self-contained respiratory protective equipment and protective clothing. • Air the room after you have extinguished the UPS. Safety labels on the UPS The following safety labels are attached to the name plate of the UPS: CU8110-0060 Version: 1.0...
  • Page 10: Transport And Storage

    Despite the robust design of the unit, the components are sensitive to strong vibrations and impacts. Therefore, during transport please protect your device from: • mechanical stress and • use the original packaging. Table 1: Dimensions and weight CU8110-0060 Dimensions (W x H x D) 50 mm x 100 mm x 90 mm Weight approx. 425 g...
  • Page 11: Product Overview

    In the event of a fault or the failure in the 24 V DC input voltage, the UPS takes over the supply of power to the connected devices with a controlled and buffered 24 V DC output voltage. All Beckhoff components or components from third parties, especially industrial PCs, embedded PCs, panels and panel PCs, can be equipped with the CU81xx UPS series.
  • Page 12: Name Plate

    Maximum power consumption and power output of the UPS. UPS capacity. Hardware and software version. Power supply 24 V DC. CE approval. Machine-readable information in the form of a Data Matrix Code (DMC, code scheme ECC200) that you can use for better identification and management. Version: 1.0 CU8110-0060...
  • Page 13: Block Diagram

    At the same time, an overvoltage warning is output. Therefore, less than 24 V and more than 28.8 V can never be present at the UPS output. The complete control of the UPS is handled by the central UPS controller, which orchestrates the interaction of all other microcontrollers (UPS-OCT communication, charge controller). CU8110-0060 Version: 1.0...
  • Page 14: Holding Times

    Fig. 4: Hold time without temperature and ageing effects. Withdrawable e nerg [Wh] = f( Output current ) [A] 0,40 0,35 0,30 0,25 0,20 0,15 0,10 0,05 0,00 0,25 0,75 1,25 1,75 2,25 Fig. 5: Usable energy without temperature and ageing effects. Version: 1.0 CU8110-0060...
  • Page 15: Interfaces

    USB 2.0 interface (X101) The USB interface is a communication interface between the UPS and Industrial PC. Die USB interface can be used especially by devices without UPS-OCT. These include, for example, older Beckhoff Industrial PCs but also components supplied by third-party providers.
  • Page 16: Power Supply (X102)

    +24 V DC output for power-fail-signal. This output is switched to 24 V if the power supply fails or if P SHDN is activated. This output can be connected with the PC_ON input on a Beckhoff Industrial PC or any PLC input.
  • Page 17: Commissioning

    Commissioning Commissioning Assembly 48,8 87,8 Fig. 8: CU8110-0060 dimensions. 48,8 Fig. 9: CU8110-0060 with mounting plate (optional), dimensions. CU8110-0060 Version: 1.0...
  • Page 18: Fastening To The Din Rail

    UPS can be attached on the upper edge of the DIN rail. 4. Attach the UPS to the upper edge of the DIN rail. ð You have successfully mounted the UPS. Check again that the mounting is correct and that the UPS is engaged on the DIN rail. Version: 1.0 CU8110-0060...
  • Page 19: Installing The Mounting Plate (Optional)

    1. Loosen the six M4 screws and remove the DIN rail adapter. 2. Loosen the M3 screws and remove the grounding springs from the UPS. 3. Fasten the mounting plate to the rear panel of the UPS with four M4 screws. CU8110-0060 Version: 1.0...
  • Page 20: Power Supply

    (-15 % / +20 %). Connect the external power supply unit to the Uin input of the UPS. Fig. 10: Schematic wiring of a CU8110-0060 UPS. The cabling of the UPS in the control cabinet must be done in accordance with the standard EN 60204-1:2006 PELV = Protective Extra Low Voltage: •...
  • Page 21: Table 9 Required Cable Cross-Sections And Strip Lengths

    Connect the devices to be supported to the U1out and U2out outputs. If the external 24 V DC input voltage is lost, the UPS takes over the supply of the devices connected to it thanks to its regulated and buffered 24 V DC output voltage. Use the two 9-pin connectors with push-in connection to wire the CU8110-0060 UPS.
  • Page 22: Communication

    6.3.1 Connection via UPS-OCT A special feature of the Beckhoff CU8110-0060 UPS is OCT (One Cable Technology) as a communication technology between UPS and Industrial PC. The two connection cables (+24 V, 0 V) between the Industrial PC and the UPS are used to supply power to the Industrial PC and for bidirectional, modulated data transmission.
  • Page 23: Connecting Additional Devices

    U2out UPS RDY X102 Shielding Grounding busbar GND P-S LAN 1 LAN 1 DP out X104 USB 2.0 X105 USB 3.0 X106 Fig. 12: Connection example when using the second USP output (U2out) for an additional Control Panel. CU8110-0060 Version: 1.0...
  • Page 24: Connection Via Usb

    UPS RDY X102 Shielding Grounding busbar Fig. 13: Example of a connection via USB with a CU8110-0060 UPS and a CX5240 Embedded PC. The USB interface conforms to the USB 2.0 standard. The cable length is limited to 5 m. Version: 1.0 CU8110-0060...
  • Page 25: Connection Via Digital I/O

    P FAIL In the case of Beckhoff Industrial PCs, the P-FAIL output of the UPS can be connected to the PC_ON input of an Industrial PC. In the event of a power failure, the P-FAIL output is set to 24 V. 24 V are thus applied to the PC_ON input of the Industrial PC and the Industrial PC is shut down properly.
  • Page 26: Configuration

    This chapter shows you how to install the Beckhoff UPS software on an Industrial PC or a non Beckhoff PC. If an older version of the UPS software is already installed, uninstall it first, since it may not be possible to update all files.
  • Page 27: System Behavior

    Configuration System behavior The settings under Alarm configuration influence the system behavior of the Beckhoff Miniport driver and affect how long the UPS supports the devices connected to it, when notifications or the critical alarm are issued. Short power failure: t <t...
  • Page 28 Maximum time on battery voltage before critical Configurable in minutes (or in seconds starting alarm. Once this time has elapsed the UPS from Windows 7 and higher) via the Beckhoff service irrevocably starts shutting down the UPS configuration dialog. system.
  • Page 29 (e.g. XP): For systems without soft power-off functionality • With Beckhoff P24Vxxxx UPS: tDlg = 0, the the dialog should be visible at least for a short UPS switches off the outputs and the IPC time before the UPS switches off the IPC.
  • Page 30: Ups Configuration Dialogs

    Power fail counter: From UPS software version >= 3.0.0.6. The counter is reset at UPS service start and counts the detected power fails. Details: Shows current configured UPS model and manufacturer name. Manufacturer name "(None)" means UPS service not configured and deactivated. Version: 1.0 CU8110-0060...
  • Page 31: Device Configuration Dialog

    Setting or Value range Default value Description function Battery Type C9900-U330, C9900-U330 Configures the used Beckhoff battery pack type. (combo box) C9900-U332, User-Defined Battery Type 0..99 Available only if "User-Defined" battery type is selected. (edit field) The setting is necessary, for instance, to be able to calculate the remaining charge available under battery operation.
  • Page 32 Defaults type setting is: C9900-U330. Please check your real battery type configuration. Saves all settings and closes the dialog. Don't forgett to apply the changes at the Beckhoff UPS Configuration dialog too. Cancel Discards all editable changes. *) Example value.
  • Page 33: Alarm Configuration Dialog

    The user have to select one of the tasks. The default task (if existing) with the name: "UPS System Shutdown Program" is selected automatically it the task is configured for the first time. CU8110-0060 Version: 1.0...
  • Page 34 OS began to shut down. Once this below) time has elapsed, the UPS switches off its outputs in order to save battery charge. Make sure that you have not selected too short a time for this. Version: 1.0 CU8110-0060...
  • Page 35 Beckhoff UPS Configuration dialog too. Cancel Discards all editable changes and closes the dialog. Delay times for switching off the UPS in seconds: • Beckhoff USB UPS: 20, 30, 45, 60, 120, 180, 300, 600 CU8110-0060 Version: 1.0...
  • Page 36: Configuring The Ups

    Configuration Configuring the UPS This step shows how to configure the UPS in the Beckhoff UPS software. Two of the most important settings that affect the behavior of the UPS in the event of a power failure are: • Max. time on battery before critical alarm •...
  • Page 37 Industrial PC is shutting down. As soon as the critical alarm is triggered, the set countdown of 180 seconds is started. The shutdown of the Industrial PC must be successfully completed within this time (180 seconds), since the outputs of the UPS are switched off directly after the 180 seconds have elapsed. CU8110-0060 Version: 1.0...
  • Page 38: Twincat Interface

    ◦ NT4, Win2K, WinXP, WinXP embedded: Additional tabs under "Control Panel->Power Options- >Beckhoff UPS Configuration" or "Control Panel->Power Options->UPS". ◦ Beckhoff CE devices with 24V UPS support are delivered with a special Beckhoff Battery Driver for Windows CE. In these devices the driver is included in the standard CE image.
  • Page 39 Development en- Target platform UPS hardware PLC libraries to be vironment integrated (cate- gory group) TwinCAT v3.1.0 PC or CX (x86, x64, ARM) • Beckhoff BAPI v1; Tc2_IoFunctions (IO) • Beckhoff P24Vxxxx; • Beckhoff CP903x card (PCI/ISA); CU8110-0060 Version: 1.0...
  • Page 40: St_Upsstatus

    Target platform UPS hardware PLC libraries to be vironment integrated (cate- gory group) • Beckhoff CX2100-09x4 models (e.g. CX2100-0904 or CX2100-0914 + "Smart Battery" CX2900-0192); • The APC devices that come supplied with Beckhoff Industrial PC support the Smart protocol and can be configured with the Windows UPS service.
  • Page 41 Configuration Status in- Beckhoff BAPI Beckhoff Beckhoff 24V CX2100-09x4 Description formation P24Vxxxx UPS UPS on the Back- Smart- CP903x card UPS 420 FirmwareR UPS firmware version information. Empty string if the UPS does not support this parameter. SerialNum None Serial number of the UPS.
  • Page 42 TwinCAT v3.1.0 PC or CX (x86, x64, ARM) • Beckhoff BAPI v1; Tc2_IoFunctions (IO) • Beckhoff P24Vxxxx; • Beckhoff CP903x card (PCI/ISA); • Beckhoff CX2100-09x4 models (e.g. CX2100-0904 or CX2100-0914 + "Smart Battery" CX2900-0192); • The APC devices that come...
  • Page 43: E_Batterystatus

    TwinCAT v3.1.0 PC or CX (x86, x64, ARM) • Beckhoff BAPI v1; Tc2_IoFunctions (IO) • Beckhoff P24Vxxxx; • Beckhoff CP903x card (PCI/ISA); • Beckhoff CX2100-09x4 models (e.g. CX2100-0904 or CX2100-0914 + "Smart Battery" CX2900-0192); • The APC devices that come...
  • Page 44: E_Upspowerstatus

    UPS hardware PLC libraries to be vironment integrated (cate- gory group) • Beckhoff P24Vxxxx; • Beckhoff CP903x card (PCI/ISA); • Beckhoff CX2100-09x4 models (e.g. CX2100-0904 or CX2100-0914 + "Smart Battery" CX2900-0192); • The APC devices that come supplied with Beckhoff Industrial...
  • Page 45: Error Handling And Diagnostics

    Green, Yellow UPS is below or above the allowed ambient temperature. Green Input voltage Uin present. UPS is ready for operation and charged. Red, flashing No input voltage Uin. UPS mode started and UPS is being discharged. CU8110-0060 Version: 1.0...
  • Page 46: Care And Maintenance

    Clean only the housing of the UPS. Use a soft, moist cleaning cloth for this. Make sure that the ventilation slots of the device are always free and do not clog up. The following cleaning agents and materials are unsuitable and may cause damage: • corrosive cleaning agents • solvents • scouring agents • hard objects Version: 1.0 CU8110-0060...
  • Page 47: 10 Decommissioning

    ð As soon as you push the UPS upwards, the lower springs of the DIN rail adapters give way. This allows the UPS to be released from the top edge of the DIN rail. 2. Tilt the UPS forwards. ð The UPS can be removed from the DIN rail. CU8110-0060 Version: 1.0...
  • Page 48: Disposal

    Decommissioning 10.2 Disposal Beckhoff Automation products are marketed exclusively to corporate customers. According to the directive 2012/19/EU "WEEE", we take old devices and accessories back for professional disposal. The transport costs are covered by the sender. Send the old devices with the note "For disposal" to: Beckhoff Automation GmbH &...
  • Page 49: 11 Technical Data

    Technical data 11 Technical data Table 13: Technical data, dimensions and weights. Technical data CU8110-0060 Dimensions (W x H x D) 50 mm x 100 mm x 90 mm Weight approx. 425 g Table 14: Technical data, general data. Technical data CU8110-0060 Type...
  • Page 50: Table 18 Technical Data, Output P_Fail And Ups_Rdy

    Technical data Table 18: Technical data, output P_FAIL and UPS_RDY. Technical data CU8110-0060 Nominal voltage 24 V (-15%/+20%) Load type ohmic, inductive, lamp load Max. output current 0.5 A (short-circuit proof) Short circuit current < 1 A typ. Output stage push (high-side switch) Max. breaking energy <...
  • Page 51: 12 Appendix

    Description C9900-M676 Mounting plate made of black anodized aluminum for UPS mounting on the control cabinet wall, suitable for CU8110-0060 C9900-P950 Replacement plug for the power supply of the CU81xx UPS series. Two 9-pin plugs with push-in connection for cables with a cross-section of 0.14 mm² to 1.5 mm²...
  • Page 52: Support And Service

    Please contact your Beckhoff branch office or representative for local support and service on Beckhoff products! The addresses of Beckhoff's branch offices and representatives round the world can be found on our internet page: www.beckhoff.com You will also find further documentation for Beckhoff components there.
  • Page 53 Table 15 Technical data, electrical currents and internal fuses..............Table 16 Technical data, power loss......................Table 17 Technical data, input UPS_EN and P_SHDN................Table 18 Technical data, output P_FAIL and UPS_RDY................Table 19 Technical data, environmental conditions..................Table 20 Mounting accessories........................CU8110-0060 Version: 1.0...
  • Page 54 Connection example when using the second USP output (U2out) for an additional Control Panel............................Fig. 13 Example of a connection via USB with a CU8110-0060 UPS and a CX5240 Embedded PC..Fig. 14 Connection example via digital I/O with an Embedded PC CX7000 with digital inputs....
  • Page 56 More Information: www.beckhoff.com/CU8110-0060 Beckhoff Automation GmbH & Co. KG Hülshorstweg 20 33415 Verl Germany Phone: +49 5246 9630 info@beckhoff.com www.beckhoff.com...