6.22 TYPE 21: ALARM INDICATING COMMUNICATION ERROR FOR ONE OF THE MODBUS
PRESSURE SENSOR
- Conditions:
• Unit with at least one configured Modbus pressure sensor.
- Causes:
• One or more of the Modbus pressure sensors give too much communication errors.
This in turn can come from:
The physical absence of one of the configured sensor.
One of the sensors is not powered on: check "ON" led of all configured sensors. See installation manual of Modbus
pressure sensor.
Faulty cable
One of the sensors address is not correctly set: check the setting wheel position for each configured sensor according to
its function. See diagnostic here below.
.
- Effects:
Displayed on HMI TACtouch
Code
D.30
MODBUS SENSOR COMMUNICATION ERROR
TAC control board
ALARM OUTPUT
AL dPa OUTPUT
/
/
Auto reset: yes
- Diagnostic:
Check in TACtouch the screen with the communication
sensor errors in menu/info: the Modbus pressure sensor
which is in alarm will have its error counter that increases
(if the screen doesn't appear, go first in menu settings/
Factory setup). Once identify, check first of all that it
is well present otherwise, it will be necessary to modify
the configuration to tell the control board that it is not
present.
If the sensor is well present, check that the address of the
wheel is correct.
Finally, check it's status led: green led on, communication
orange blinking. If status led are different, then it may
be due to the cable or to sensor itself that is damaged.
Wiring is in chain from connector RJ3 or RJ4 for sensors 1
(kit CA supply), 2 (kit CA exhaust) and C (defrost), from
connector RJ2 for sensor 5 (CP mode supply) and 6 (CP
mode exhaust). See TAC wiring overview at point 4:
32
www.swegon.com
GB.ESENSA.MO.231025
Text displayed
LED ALARM
Fans
ON
/
We reserve the right to alter specifications.
6.23 TYPE 22: ALARM INDICATING THAT THE HOURS LIMIT FOR THE MAJOR MAINTENANCE
HAS BEEN REACHED
- Conditions:
• The hours limit must be configured with a value greater than 0.
- Causes:
• The hours limit for the major maintenance has been reached.
The instructions in this manual for the 12 months maintenance should be followed.
Reset the hours for major maintenance after this operation, this will reset automatically the alarm and give it again after the
same period. Reset also minor maintenance hours.
Effects:
Code
M.11
ALARM OUTPUT
Level
/
1
We reserve the right to alter specifications.
Displayed on HMI TACtouch
Text displayed
MAJOR MAINTENANCE ALARM
TAC control board
AL dPa OUTPUT
LED ALARM
/
ON
Auto reset: via dedicated reset