Carrier SmartVu 61AF 030-105 Manual page 17

Hide thumbs Also See for SmartVu 61AF 030-105:
Table of Contents

Advertisement

5 - USER INTERFACE: MENU STRUCTURE
OUTPUTS – Outputs (continued)
No. Name
Status
15
PUMP_1
off / on
16
PUMP_EXT
0 to 10
17
ALARM
off / on
18
RUNNING
off / on
19
DHW_3WV
off / on
*Depends on the selected language (English by default).
PUMPSTAT – Pump Status
No. Name
Status
1
2
drvp_pct
-
3
drvp_pwr
-
4
drvp_i
-
5
drvp_ver
-
6
7
PUMP_EXT
0 to 100
*Depends on the selected language (English by default).
RUNTIME – Runtime
No. Name
Status
1
hr_mach
-
2
st_mach
-
3
hr_cp_a1
-
4
st_cp_a1
-
5
hr_cp_a2
-
6
st_cp_a2
-
7
hr_fana1
-
8
hr_fana2
-
9
hr_pump1
-
*Depends on the selected language (English by default).
MODES – Modes
No. Name
Status
1
m_limit
no/yes
2
m_ramp
no/yes
3
m_cooler
no/yes
4
m_leadla
no/yes
5
m_heater
no/yes
6
m_boiler
no/yes
7
m_summer
no/yes
8
m_dhw
no/yes
9
m_defr_a
no/yes
10
m_spedfr
no/yes
11
m_sst_a
no/yes
12
m_dgt_a
no/yes
13
m_hp_a
no/yes
14
m_sh_a
no/yes
*Depends on the selected language (English by default).
Unit
Displayed text*
-
Pump 1 Output
V
External Pump Output
-
Alarm Relay Status
-
Running Relay Status
-
Domestic Hot Water Valve
Unit
Displayed text*
DRIVE PUMP STATUS
%
Pump Drive Percent
kW
Pump Drive Power
A
Pump Drive Amps
-
Pump Drive Version
0-10V PUMP STATUS
%
External Pump Output
Unit
Displayed text*
hour
Machine Operating Hours
-
Machine Starts Number
hour
Compressor A1 Hours
-
Compressor A1 Starts
hour
Compressor A2 Hours
-
Compressor A2 Starts
hour
Circuit A Fan #1 Hours
hour
Circuit A Fan #2 Hours
hour
Water Pump Hours
Unit
Displayed text*
-
Demand Limit Active
-
Ramp Loading Active
-
Cooler Heater Active
-
Master Slave Active
-
Electric Heat Active
-
Boiler Active
-
Summer Active
-
DHW Active
-
Defrost Active
-
Special Defrost Active
-
Low Suction
-
Compressor Envelope
-
High Pressure Override
-
Low SuperHeat
Description
Pump 1 output (internal pump)
External pump output
Alarm relay status
Running relay status
Domestic hot water valve
Description
Drive pump status
Pump drive percent
Pump drive power
Pump drive amps
Pump drive version
0-10V pump status
External pump output
Description
Machine operating hours
Number of machine starts
Operating hours, compressor A1
Number of starts, compressor A1
Operating hours, compressor A2
Number of starts, compressor A2
Operating hours, fan 1
Operating hours, fan 2
Operating hours, water pump
Description
Demand limit active
Ramp loading active
Exchanger heater active
(optional)
Master/Slave active
Electric heating active
Boiler active
Summer mode active
DHW mode active
Defrost mode active
Free defrost mode active
Low suction temperature protection active
(unit capacity cannot be increased)
Compressor envelope protection active
(unit not allowed to start if water temperature is out of range)
High pressure override active
Low superheat protection is active (unit will not be started)
17

Advertisement

Table of Contents
loading

This manual is also suitable for:

Smartvu 61af 022-105

Table of Contents