Panduit M1 Installation Manual

Intelligent pdu

Advertisement

Quick Links

M1 Intelligent PDU Installation Manual
V1.1

Advertisement

Table of Contents
loading

Summary of Contents for Panduit M1

  • Page 1 M1 Intelligent PDU Installation Manual V1.1...
  • Page 2: Table Of Contents

    Mounting Hardware Installation ................12 Grounding the PDU ........................... 13 Connecting the Ground Bonding Cable ..............13 Bonding ........................14 Section 3 – Connecting the PDU ..................15 Connecting the PDU to a Power Source ..............15 M1 INTELLIGENT PDU INSTALLATION MANUAL...
  • Page 3: Before You Begin

    Important Safety Information See the complete regulatory compliance notices in Safety and Compliance Information for Server, Storage, Power, Networking, and Rack Products on the Panduit website (http://www.panduit.com/). In addition, follow the safety precautions that are specific to this device.
  • Page 4 Be sure all circuit breakers are in the off position before connecting input power. Be sure that the devices connected to the Panduit PDU are adjusted for, or otherwise capable of, operation from the same line voltage supplying the PDU.
  • Page 5: Required Tools

    Required Tools The following tools maybe required for installation: Phillips screwdriver Torx screwdriver M1 INTELLIGENT PDU INSTALLATION MANUAL...
  • Page 6: Section 1 - Introduction

    Web interface, or a Command Line Interface (CLI), and viewed from the local display. Panduit PDUs are designed for use with all Panduit cabinets and are compatible with most third-party data center racks. The PDU models vary in form factor with several mounting configurations available.
  • Page 7: Features

    Panduit Monitored & Switched per Outlet PDU: Provides outlet-level power monitoring and outlet-level switching capabilities for individual outlets or a group of outlets. Power monitoring at the individual outlet level provides actionable management data on the power consumption of each connected IT device, enabling the redeployment or decommissioning of individual servers to reclaim available or under- utilized power capacity.
  • Page 8: Form Factors

    Load Segment and Phase Distinction Panduit Essential PDUs have colored receptacles to help distinguish between the different load segments and phases. All Panduit three phase PDUs have different colored receptacles (white, dark gray, and black) to distinguish the different phases. All Panduit PDUs with breakers have different colored receptacles to distinguish the different load segments (with one exception as noted below).
  • Page 9: Section 2 - Installing The Pdu

    Install Mounting Hardware Each vertical PDU has two mounting hole locations on the back of the PDU for the button installation to assist with mounting in a non-Panduit racks. When installing the mounting buttons, use either mounting hole as a set.
  • Page 10: Install Bracket Hardware (Brk01 - Optional)

    Each vertical PDU can install the optional bracket with provided screws on the end of the PDU. 1. Align and install the bracket with the screw holes on the end of PDU, fix with provided screws. 2. Install to the rack with provided four (4) M5x10mm self-tapping screws. M1 INTELLIGENT PDU INSTALLATION MANUAL...
  • Page 11: Vertical (0U) Pdu- Single Installation

    NOTE: (A) Two full-height PDUs with outlets facing in towards the center of the rack; (B) Two mid-height PDUs with outlets facing in towards center of the rack; (C) Four half- height PDUs with outlets facing in towards center of the rack. M1 INTELLIGENT PDU INSTALLATION MANUAL...
  • Page 12: 1U Pdus

    1U PDU Mounting in a U Position of the Rack 1. Install the cage nuts at the desired U location. 2. Screw the mounting bracket ears into the RETMA rail surface at the U location where the cage nuts were installed. M1 INTELLIGENT PDU INSTALLATION MANUAL...
  • Page 13: Grounding The Pdu

    These models have the ground bounding point on the surface with the circuit breakers. Bond Power Distribution Units (PDUs) to grounding strip or grounding bus bar. See Panduit Grounding and Bonding Jumper kits for factory terminated options to provide a bolt-on solution.
  • Page 14: Bonding

    Earth bonding to the rack metalwork. Bonding Minimum Requirements for Bonding Conductors Up to and including 32A 12 AWG Screw Size Over 16A, less than or equal to 40A M1 INTELLIGENT PDU INSTALLATION MANUAL...
  • Page 15: Section 3 - Connecting The Pdu

    PDU operating system is loading. When complete, the Main Menu will display on the LCD screen. Switched and Monitored & switched PDUs show a light corresponding to each outlet as it is powered up. M1 INTELLIGENT PDU INSTALLATION MANUAL...