PDU8000 DC Combiner Cabinet
User Manual
Model
BOM number
Dimensions (H
x W x D)
Net weight/
Gross weight
Rated
operating
voltage
Rated
insulation
voltage
Rated
operating
current
Number of
outputs
Output circuit
current
Insulation
monitoring
function
IP rating
Surge
protection
level
Issue 02 (2022-08-10)
3
PDU8000-1250D9-BS310
02407384
2000 mm x 800 mm x 600 mm
229 kg/259 kg
800 V DC
1000 V DC
1250 A
8
≤ 250 A
Bus insulation monitoring and 8-branch locating
● Insulation resistance measurement range: 1–100 kΩ
● Detection precision: ≤ 10%
● Response time: ≤ 120s
IP20
I
= 20 kA