Troubleshooting - Huawei PDU8000 User Manual

Dc combiner cabinet
Hide thumbs Also See for PDU8000:
Table of Contents

Advertisement

PDU8000 DC Combiner Cabinet
User Manual
Symptom
The RUN
indicator for the
insulation
monitoring
instrument is
off.
The ALA
indicator for the
insulation
monitoring
instrument is
on.
The leakage
current sensor
indicator for a
branch is off.
Issue 02 (2022-08-10)
Possible Causes
● The PSU for the insulation
monitoring instrument is faulty.
● The upstream fuse for the PSU of
the insulation monitoring
instrument is faulty.
● The cables to the J2 terminals HM
+, HM–, and PE on the insulation
monitoring instrument are
reversely connected.
● The insulation between the positive
and negative buses and the ground
is abnormal.
● The sequence of wiring from the
insulation monitoring instrument
to the leakage current sensor is
incorrect.
● The leakage current sensor is
faulty.
Copyright © Huawei Digital Power Technologies Co., Ltd.
7

Troubleshooting

7 Troubleshooting
Troubleshooting
● Replace the PSU
or its fuse.
● Connect the
cables in the
correct sequence.
● Check whether
the upstream
power supply,
downstream
loads, and input
and output cables
are damaged or
short-circuited to
the ground. If so,
replace the
cables.
● Connect the
cables in the
correct sequence.
● Replace the
leakage current
sensor.
50