Toshiba MMK-UP0051DHPL-E(TR) Service Manual page 89

Table of Contents

Advertisement

9-5. Sensor Characteristics
Indoor Unit
Temperature sensor characteristics
Indoor TA sensor
30
20
Resistance
[k ]
10
0
Indoor TC1 sensor
200
150
Resistance
[k ]
100
(Below 10˚C)
50
0
-30
-20
200
150
Resistance
[k ]
100
(Below 10˚C)
50
0
-30
-20
10
20
30
40
Temperature [˚C]
-10 0 10 20 30 40 50 60 70 80 90 100
Temperature [˚C]
-10 0 10 20 30 40 50 60 70 80 90 100
Temperature [˚C]
50
60
20
15
Resistance
[k ]
10
(Above 10˚C)
5
20
15
Resistance
[k ]
10
(Above 10˚C)
5
- 89 -
Temperature
Resistance
value [k ]
[C˚]
0
33.9
5
26.1
10
20.3
15
15.9
20
12.6
25
10.0
30
8.0
35
6.4
40
5.2
45
4.2
50
3.5
55
2.8
60
2.4
Resistance
Temperature
[C˚]
value [k ]
-20
99.9
-15
74.1
-10
55.6
-5
42.2
0
32.8
5
25.4
10
19.8
15
15.6
20
12.4
25
10.0
30
8.1
35
6.5
40
5.3
45
4.4
50
3.6
55
3.0
60
2.5
65
2.1
70
1.8
75
1.5
80
1.3
85
1.1
90
1.0
95
0.8
100
0.7
Temperature
Resistance
[C˚]
value [k ]
-20
115.2
-15
84.2
-10
62.3
-5
46.6
0
35.2
5
26.9
10
20.7
15
16.1
20
12.6
25
10.0
30
8.0
35
6.4
40
5.2
45
4.2
50
3.5
55
2.8
60
2.4
65
2.0
70
1.6
75
1.4
80
1.2