Toshiba MMK-UP0051DHPL-E(TR) Service Manual page 57

Table of Contents

Advertisement

To change all the indoor unit addresses using an arbitrary wired remote controller.
(The method is available when the addresses have already been set automatically.)
(When communication wirings of 2 or more refrigerant lines are interconnected for central control)
NOTE
You can change the addresses of indoor units in each refrigerant line using an arbitrary wired remote controller.
* Enter the address check / change mode and change the addresses.
<RBC-AMTU
>
TEMP.
1
FILTER
RESET
TEST
3
Cancels the line selection
If no number appears on UNIT No., no outdoor unit exists on the line. Push button and select another line
2
following step
.
(Execute it while the units are stopped.)
1
Push and hold the TIME
At first, the line 1 and CODE No.
UNIT LOUVER
2
Push
button (left side of the button) and
address.
3
Push the
button.
• The address of one of the indoor units connected to the selected refrigerant line is indicated on the LCD display and
the fan and louvers of the unit are activated.
At first, the current indoor unit address is displayed in SET DATA.
(No system address is indicated.)
4
Push the TIME
SET DATA.
Change the value in SET DATA to that of a new address.
5
Push the
button to confirm the new address on SET DATA.
UNIT LOUVER
6
Push the
button (left side of the button) repeatedly to select another address to
change.
Each time you push the button, the indoor unit numbers in a refrigerant line are indicated
one after another. Only the fan and louvers of the selected indoor unit are activated.
4
6
Repeat steps
to
to change the indoor unit addresses so as to make each of them unique.
7
Push the
button.
(All the segments on the LCD display light up.)
8
Push the
button to finish the procedure.
<RBC-ASCU11- >
There is no such function in the remote controller.
ON / OFF
TIMER SET
FAN
MODE
TIME
SAVE
VENT
SET
CL
SWING/FIX
UNIT LOUVER
2
/
buttons at the same time for more than 4 seconds.
AC AC AC AC AC
(Address Change) are indicated on the LCD display.
/
buttons repeatedly to change the value of the indoor unit address in
TEMP.
TIMER SET
4
TIME
FILTER
RESET
TEST
SET
CL
8
Finish
5, 7
Press to finish
setting
SWING/FIX
buttons repeatedly to select a system
- 57 -
ON / OFF
FAN
MODE
SAVE
VENT
SWING/FIX
UNIT LOUVER
6

Advertisement

Table of Contents
loading

Table of Contents