8-2. Applied control of indoor unit
Control system using Remote location ON/OFF control box (TCB-IFCB-4E2)
Wiring and setting
• In the case of group control, the control system functions as long as it is connected to one of the indoor units
(control P.C. board) in the group. If it is desired to access the operation and trouble statuses of other units,
relevant signals must be brought to it from those units individually.
1. Control items
(1) Start / Stop input signal
(2) In-operation signal
(3) Check code Output
2. Wiring diagram of control system using Remote location ON/OFF control box (TCB-IFCB-4E2)
Input
IFCB-4E2: No-voltage ON / OFF serial signal
Output
No-voltage contact (in-operation and check code indication)
Contact capacity: Max. AC 240 V, 0.5 A
Indoor control P.C. board
Start/Stop input
Remote controller disabling / ending input
In-operation signal output
Check code output
Start / stop of unit
Output present while unit in normal operation
present while alarm (e.g. serial communication trouble or operation of
protective device for indoor / outdoor unit) being activated
1
COM (GND)
2
3
4
COM (+12V)
5
6
CN61
T10
(Yellow)
TCB-IFCB-4E2
1
2
3
4
CN06
1
2
3
4
5
6
CN13
Power supply 220-240V
- 42 -
ON side
Start signal input
OFF side
Stop signal input
COM
In-operation signal output
Check code output