How to fix the drain hose
• To install the drain hose, insert the drain hose firmly
until the connection part contacts with heat insulator,
secure push steel plate of drain hose to predetermined
position of Drain pan then fix it by original screw.
When removing or install the drain hose, be careful of any sharp edges of steel plate. The edges can
cause injuries.
How to remove the drain cap
• Clip the drain cap by needle-nose pliers and pull out.
How to fix the drain cap
• Insert hexagonal wrench (dia. 4 mm) in a center head.
• Firmly insert the drain cap.
Firmly insert the drain hose and drain cap; otherwise, water may leak.
Drain pan
Drain hose
CAUTION
Needle-nose pliers
Do not apply lubricating oil
(refrigerant machine oil)
when inserting the drain
cap. Application causes
deterioration and drain
leakage from the plug.
CAUTION
- 110 -
Heat insulator (foam)
Cap drain
Hexagonal wrench
Insert a hexagon wrench
No gap
(4 mm).