Trane 5TEM6B02AV21SA Installation, Operation And Maintenance Manual page 25

Convertible air handlers
Table of Contents

Advertisement

No. of
Heater Model No.
Circuits/
Phases
No Heater
BAYHTR1504BRK
1/1
BAYHTR1504LUG
BAYHTR1505BRK
1/1
BAYHTR1505LUG
BAYHTR1508BRK
1/1
BAYHTR1508LUG
BAYHTR1510BRK
1/1
BAYHTR1510LUG
BAYHTR1517BRK
Circuit 1
(a)
2/1
BAYHTR1517BRK
Circuit 2
BAYHTR1523BRK
Circuit 1
2/1
BAYHTR1523BRK
Circuit 2
1/3
BAYHTR3510LUG
1/3
BAYHTR3517LUG
* = Motor Amps
(a)
MCA and MOP for circuit 1 contains the motor amps
No. of
Heater Model No.
Circuits/
Phases
No Heater
BAYHTR1504BRK
1/1
BAYHTR1504LUG
BAYHTR1505BRK
1/1
BAYHTR1505LUG
BAYHTR1508BRK
1/1
BAYHTR1508LUG
BAYHTR1510BRK
1/1
BAYHTR1510LUG
BAYHTR1517BRK
Circuit 1
(a)
2/1
BAYHTR1517BRK
Circuit 2
BAYHTR1523BRK
Circuit 1
2/1
BAYHTR1523BRK
Circuit 2
BAYHTR1525BRK
Circuit 1
BAYHTR1525BRK
Circuit 2
4/1
BAYHTR1525BRK
Circuit 3
BAYHTR1525BRK
Circuit 4
1/3
BAYHTR3510LUG
1/3
BAYHTR3517LUG
* = Motor Amps
(a)
MCA and MOP for circuit 1 contains the motor amps
18-GF79D1-1A-EN
5TEM6D04AV31SAA/5TEM6D05AV41SAA HEATER DATA
240 Volt
Capacity
Heater
Amps per
kW
BTUH
Circuit
4.3 *
3.84
13100
16.0
4.80
16400
20.0
7.68
26200
32.0
9.60
32800
40.0
9.60
32800
40.0
4.80
16400
20.0
9.60
32800
40.0
9.60
32800
40.0
9.60
32800
23.1
14.40
49100
34.6
5TEM6D06AV41SAA/5TEM6D07AV51SAA HEATER DATA
240 Volt
Capacity
Heater
Amps per
kW
BTUH
Circuit
6.8 *
3.84
13100
16.0
4.80
16400
20.0
7.68
26200
32.0
9.60
32800
40.0
9.60
32800
40.0
4.80
16400
20.0
9.60
32800
40.0
9.60
32800
40.0
6.00
20500
25.0
6.00
20500
25.0
6.00
20500
25.0
6.00
20500
25.0
9.60
32800
23.1
14.40
49100
34.6
P P e e r r f f o o r r m m a a n n c c e e a a n n d d E E l l e e c c t t r r i i c c a a l l D D a a t t a a
Minimum
Capacity
Maximum
Circuit
Overload
kW
Ampacity
Protection
5
15
25
25
2.88
30
30
3.60
45
45
5.76
55
60
7.20
55
60
7.20
25
25
3.60
55
60
7.20
50
50
7.20
34
35
7.20
10.8-
48
50
0
Minimum
Capacity
Maximum
Circuit
Overload
kW
Ampacity
Protection
9
15
29
30
2.88
34
35
3.60
49
50
5.76
59
60
7.20
59
60
7.20
25
25
3.60
59
60
7.20
50
50
7.20
40
40
4.50
31
35
4.50
31
35
4.50
31
35
4.50
36
40
7.20
51
60
10.80
208 Volt
Minimum
Heater
Circuit
Amps per
BTUH
Ampacity
Circuit
4.3 *
5
9800
13.8
23
12300
17.3
27
19700
27.7
40
24600
34.6
49
24600
34.6
49
12300
17.3
22
24600
34.6
49
24600
34.6
43
24600
20.0
30
36900
30.0
42
208 Volt
Minimum
Heater
Circuit
Amps per
BTUH
Ampacity
Circuit
6.8 *
9
9800
13.8
26
12300
17.3
30
19700
27.7
43
24600
34.6
52
24600
34.6
52
12300
17.3
22
24600
34.6
52
24600
34.6
43
15400
21.6
36
15400
21.6
27
15400
21.6
27
15400
21.6
27
24600
20.0
33
36900
30.0
45
Maximum
Overload
Protection
15
25
30
40
50
50
25
50
45
30
45
Maximum
Overload
Protection
15
30
30
45
60
60
25
60
45
40
30
30
30
35
45
25