Advertisement

Quick Links

REACT V BMPa
Instructions for Use
Symbol key
Symbols on the machine
This product complies with
applicable EU directives
Symbols in this user manual
Warning/Caution!
Risk of crushing
Application area
The product is a variable flow damper or constant flow damper
designed for comfort ventilation indoors. The product is used to
regulate the supply air or extract air flow in ventilation ducts.
The product may not be used for anything other than its intended
use.
General
Read through the entire instructions for use before you
install/use the product and save the instructions for
future reference. It is not permissible to make changes
or modify this product other than those specified in this
document.
The packaging contains the following items
1 x REACT V BMP
1 x Instructions for use
Protective equipment
Always use appropriate personal protective equipment
for the work in question, in the form of gloves, respirators
and protective glasses during handling, installation,
cleaning and service/maintenance.
Electrical safety
Permitted voltage, see "Electrical data". It is not
permissible to insert foreign objects into the product's
contactor connections or the electronics's ventilation
openings; risk for short circuiting.
24 V isolation transformer to be connected should comply with
the provisions of IEC 61558-1.
Cable sizing must be carried out for cabling between the product
and the power supply source.
Disconnect the power supply when working on products that
are not required to run in production.
Always follow the local/national rules for who shall be permitted
to carry out this type of electrical installation.
The document was originally written in Swedish
Other risks
When the product is voltage fed, the damper will either
open or close. This can entail a certain risk of pinch
injuries to the fingers, for example, if these are placed
between the damper blade and ventilation duct when
the damper blade is rotating. The product's actuator
is equipped with a release button that permits manual
control of the damper blade, always ensure this is activated
before working on the internal parts of the damper.
Handling
• Always use appropriate transport and lifting devices when the
product is to be handled to reduce ergonomic loads.
• The product must be handled with care.
• It is not permissible to carry the product by the measuring
tube.
Installation
• Moist, cold and aggressive environments must be avoided.
• Avoid installing the product near a heat source.
• Assemble the product according to applicable industry
regulations.
• Install the product so that it is not accessible by unauthorized
persons, for example above a suspended ceiling.
• Install the product for easy access during service/maintenance.
• Supplement the duct system with a cleaning hatch in the
vicinity of the product to facilitate cleaning.
• If the product is mounted above a fixed ceiling, the inspection
hatch must be located so that the product is accessible for
inspection.
• If the product is mounted so that it is possible to gain access
to the inside of the product, it must be supplemented with
appropriate protection, for example, a ventilation unit.
• If the product is mounted in cold areas, the whole product
must be insulated on the outside against condensation.
• For installation, the accessory FSR is recommended.
• The product can be installed position independent.
• It is recommended that the product be installed so that the
front is visible.
• The product must be laid down prior to installation so that it
cannot fall over.
• Check to make sure that the product does not have any
visible defects.
• Make sure that the product is properly secured after it has
been installed.
• Use the product's eyes to secure the cables with cable ties.
• Make sure all cables are properly secured after installation.
• Check that the actuator/controller is properly mounted.
20230929
Art. 1546132

Advertisement

Table of Contents
loading

Summary of Contents for Swegon REACT V BMPa

  • Page 1 REACT V BMPa Instructions for Use 20230929 Art. 1546132 Symbol key Other risks When the product is voltage fed, the damper will either Symbols on the machine open or close. This can entail a certain risk of pinch This product complies with...
  • Page 2 300 1080 636 2920 10512 6187 Vnom at 120 Pa in pressure reading. Installed according to the instructions. Ø Figure 1. Dimensions (mm), REACT V BMP circular. The damper can be installed at an optional angle. Swegon reserves the right to alter specifications. 20230929...
  • Page 3: Installation

    Image 1-5 require no straight duct section (image 3 illustrates a T piece with a cleaning hatch). Image 6 requires a straight duct section before the damper equivalent to 4 x the diameter of the duct. 20230929 Swegon reserves the right to alter specifications.
  • Page 4 1200 x 700 41.0 1446 5206 3064 7923 28523 16787 1400 x 700 46.1 1688 6077 3577 9243 33275 19584 Vnom at 120 Pa in pressure reading. Installed according to the instructions. Swegon reserves the right to alter specifications. 20230929...
  • Page 5 Straight duct section requirements in case of sound attenuator with baffle Figure 7. Straight duct section requirements 3 x B in case of sound attenuator with baffle. Applies to both supply and extract air. 20230929 Swegon reserves the right to alter specifications.
  • Page 6 Negative half-wave, only AC Mode 2-10 V: Closed damper < 0.1 V WH OG Figure 8. Wiring diagram. – Additional actuators and sensors (max. 8). WH OG Figure 9. Wiring diagram MP-Bus. Swegon reserves the right to alter specifications. 20230929...
  • Page 7 Settings and diagnostics for the actuator can be carried out using Belimo PC-Tool or the hand-held terminal ZTH EU. When using the PC-Tool software, ZTH EU (USB) acts as an interface converter. 20230929 Swegon reserves the right to alter specifications.
  • Page 8 Available in expert mode Activation of expert mode Number of metres above sea level Available in advanced mode Setting of MP address Activation of advanced mode Duration of background lighting Clearing of the memory Swegon reserves the right to alter specifications. 20230929...
  • Page 9: Troubleshooting

    (1) the product is repaired, modified or changed, unless such repair, modification or change has been approved by Swegon AB; or (2) the serial number on the product has been made illegible or is missing.
  • Page 10: Performance Checks

    – V 8 V DC • Calculation of the current actual value (U) when you know the value of the current flow (V U = 2 V DC + 8 V DC Swegon reserves the right to alter specifications. 20230929...
  • Page 11 Note! Positioning of the damper blade and locking strip, see figures 17 and 18. Figure 17. Recess in the damper spindle indicates the position of the Figure 18. Damper open. Jumper to the left. damper. 20230929 Swegon reserves the right to alter specifications.
  • Page 12: Technical Data

    3.0 W 5.0 VA REACT V BMP 20 Nm 3.0 W 5.5 VA References www.swegon.com Building Materials Declaration REACT V BMP Product data sheet REACT Belimo – Description of functions & wiring diagram Swegon reserves the right to alter specifications. 20230929...

Table of Contents