The Tester uses these formulas to measure insulation parameters and display
the results:
Ohm's Law
Capacitance
(Charge)
PI
(Polarization Index)
DAR
(Dielectric Absorption Ratio)
DD
(Dielectric Discharge)
32
V
R =
I
Q
C
V
R
10
min
PI =
R
1
min
R
1
min
DAR
[CN]
R
15
s
I
DD
=
V
×
C
I = current after 1-minute discharge
V = voltage before discharge