3-pole Selective Earth Resistance Measurement with
A
Current Clamp
The R
3-pole Selective Earth Resistance Measurement with Current Clamp
A
procedure is useful for measuring the resistance of different parallel sections of
an earth/ground system. Refer to Figure 6.
Select function R
A
Display as shown below.
Connect test leads.
B
Connect the supplied test lead (1.5 m) to terminal E/C1 and its other
end to the ground system to be measured. Place 2 ground stakes in
earth/dirt. Minimum distance between earth electrode (E/C1), probe
(S/P2) and auxiliary earth (H/C2) should be at least 20 m!
Connect stakes with 25 m and 50 m wires to H/C2 and S/P2 as
shown. Connect current clamp with adapter cable as shown.
Press START.
C
The "active" symbol indicates that measurement is in progress. For
continuous measurement keep START pressed.
Symbol " " indicates completed measurement. The result is kept on
D
display until a new measurement is started or the rotary switch is
turned.
3
Figure 6. R
3-pole Selective Earth Resistance Measurement with Current
A
10
Shop for Fluke products online at:
3-pole A.
A
2
m
a
x
0 5
V
E
S
H
l p
s u
FLUKE
Clamp
MyFlukeStore
www.
P
2
S
4
a
c
t
v i
e
E
S
H
E
S
H
edv005.eps
1.877.766.5412
.com

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents