Physical Data And Electrical Data - Carrier AquaSnap 61AF-A Installation, Operation And Maintenance Instructions

High-temperature heat pumps
Table of Contents

Advertisement

61 AF

Physical data and electrical data

Table I: Physical data
61AF
(1)
Operating weight
Standard unit (without hydronic kit)
Standard unit (plus hydronic module option)
Sound levels
Sound power level
(2)
Sound pressure level at 10 m
(3)
Compressor
Quantity
Number of capacity stages
Refrigerant
Charge
Capacity control
Minimum capacity
Condenser
Water volume
Max. water-side operating pressure without hydronic module
Max. water-side operating pressure with hydronic module
Fan
Quantity
Total air flow (high speed)
Speed
Evaporator
Pump
Water connections with/without hydronic module
Connection Type (M male/ F female)
Connections
Nominal diameter
(1)
Weight shown is a guideline only. Please refer to the unit nameplate
(2)
In dB ref=10-12 W, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871
(with an associated uncertainty of +/3dB(A)). Measured in accordance with ISO 9614-1 and certified by Eurovent.
(3)
In dB ref 20µPa, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871
(with an associated uncertainty of +/3dB(A)). For information, calculated from the sound power level Lw(A).
Table II: Electrical data
61AF - standard unit
Power circuit
Nominal power supply
Voltage range
Control circuit supply
Maximum start-up current (Un)*
Standard unit
Unit with electronic starter option
Unit power factor at maximum capacity**
Maximum unit power input**
Nominal unit current draw***
Maximum unit current draw (Un)****
Maximum unit current draw (Un-10%)†
*
Maximum instantaneous start-up current (maximum operating current of the pump + fan current + locked rotor current of the compressor).
** Power input, compressor and fan, at the unit operating limits (saturated suction temperature 10°C, saturated condensing temperature 65°C)
and nominal voltage of 400 V (data given on the unit nameplate).
*** Standardised Eurovent conditions: condenser entering/leaving water temperature = 40°C/45°C, outside air temperature db/wb = 7°C/6°C.
****Maximum unit operating current at maximum unit power input and 400 V (values given on the unit nameplate) for tri phase and 230V for
mono phase.
Maximum unit operating current at maximum unit power input and 360 V for tri phase and 207 V for mono phase.
GB - 2
kg
kg
dB(A)
dB(A)
kg
teqCO2
%
l
kPa
kPa
l/s
r/s
inch
mm
Without PUMP
014X7
014X9
V-ph-Hz
230-1-50
400-3-50
V
207-253
360-440
24 V, via internal transformer
A
-
66
A
47
-
0.82
0.82
kW
6.4
5.9
A
22.9
7.9
A
30.7
10.8
A
36.4
11.9
014-7
014-9
159
159
169
169
71
71
43
43
Hermetic scroll 48.3 r/s
1
1
1
1
R-407C
R-407C
4,0
4,0
7.1
7.1
Pro-Dialog+
100
100
Direct-expansion plate heat exchanger
3,7
3,7
300
300
300
300
Axial twin-speed fans
2
2
2050
2050
11.7
11.7
Grooved copper tubes and aluminium fins
Variable speed pump
F
F
1
1
25
25
019X9
014H7
400-3-50
230-1-50
360-440
207-253
24 V, via internal transformer
102
-
-
48
0.82
0.82
8.8
6.5
12.4
24.0
16.0
31.8
16.6
37.5
019-9
206
216
72
44
1
1
R-407C
8,0
14.2
100
3,9
400
400
2
2000
14.5
M, M
1 IN, 1 1/4 OUT
25 IN, 32 OUT
With PUMP
014H9
019H9
400-3-50
400-3-50
360-440
360-440
67
103
-
-
0.82
0.82
6.0
8.9
9.0
13.5
11.9
17.1
13.0
17.7