s-AIRME 7500 HR-P Δp = 500 Pa Ecodesign information requirements
Manufacturer's name
Model
Typology
Type of HRS
Thermal efficiency of heat recovery
Nominal flow rate
SFP
int
SFP
limit
int
Face velocity
Maximum external leakage rate (-400Pa)
Maximum external leakage rate (+400Pa)
Maximum internal leakage rate (+250Pa)
Sound power level
Internet address for disassembly instructions
Type of drive for variable speed
Nominal flow rate
Effective electric power input
Nominal external pressure
Internal pressure drop of ventilation components
Static efficiency of fan in accordance with Regulation (EU) No
327/2011
(1)
Filter energy class
(1) = According to Eurovent 4/21
Installation, use and maintenance manual
Mitsubishi Electric Hydronics & IT Cooling
Systems S.p.A.
s-AIRME 7500 HR-P
NRVU, BVU
Cross flow heat recovery
[%]
74,6
[m³/s]
2,08
[W/(m³/s)]
812
[W/(m³/s)]
848
[m/s]
1,43
[%]
1,69
[%]
1,85
[%]
0,5
79
[db(A)]
https://www.melcohit.com/en
SUPPLY AIR FLOW
Installed
[m³/s]
2,08
[kW]
3,09
[Pa]
500
[Pa]
521
[%]
68,9
A
EXHAUST AIR FLOW
Installed
2,08
2,41
500
313
70,4
-
82