INFORMATION:
In the case of accessories and options (for example a humidifier module or a mixing module), the clearances must
be calculated considering the maximum overall dimensions with all the accessories/options provided.
Check the dimensions of the accessories/options in the relevant chapter.
The distance between the s-AIRME-G02/G07 units and the Mr. Slim condensing units should be such that the length of
the connections of the cooling circuits does not exceed 30 m.
Connections of the cooling circuits exceeding 30 m can reduce the performance of the unit and cause irreparable
damage to, or malfunctioning of the connected machines.
The connections of the cooling circuits between the s-AIRME-G02/G07 and Mr Slim must be protected against
damage.
Maximum length of piping (A) = 30 m
INFORMATION:
In the case of accessories and options, the clearances must be calculated considering the maximum overall
dimensions with all the accessories/options provided.
When two units are set side by side on the battery side, add up the measurements to be respected on the battery
side of the two units.
INFORMATION:
R32 gas is classified as slightly flammable.
In case of leakage, in order to ensure a refrigerant concentration below the safety limit, the installer/maintenance
technician must provide adequate ventilation.
INFORMATION:
Air-cooled machines must be protected against wind, which can affect condensation control
prevent defrosting in the heat pumps. The finned coils must also be protected against dirt (dust, leaves, wood chips,
etc...) and atmospheric conditions that can cause corrosion.
WARNING:
Maintenance technicians must only work on the unit's controls. They should not open any panels, other than the
access panel to the control module.
The installer must limit him/herself to connecting the plant to the unit.
Access the unit using the relative personal protective equipment and only after having read and understood the
documents and instructions, which must always be kept close at hand.