Optional extras on additional section
For the s-AIRME range, most of the optional extras are designed as additional sections to be attached to the base
unit in the order shown in the picture below.
A
LEGEND:
A: 3-way mixing chamber (only for HR-P function)
B: Photocatalytic oxidation sanitation system (PCO)
C: Electric/water post-heating
D: Humidifier
E: Aphonic septa
F: Absolute filters
G: Safety damper (delivery)
Electric pre-heating coil (option mounted in the machine)
In the case of a particularly cold winter the machine must be equipped with the optional "Electric pre-heating coil" which helps
to prevent freezing. The unit's control system is tripped automatically when the outdoor air temperature drops below -10 °C,
activating the three stages of operation of the coil to increase the air temperature up to 5 °C.
ELECTRIC PRE AND POST-HEATING COILS (CAPACITY CALCULATED FOR A TEMPERATURE DELTA = 5°C)
ELECTRIC PRE-HEATING COILS
CONSTRUCTION SPECIFICATIONS:
- IP55
- GALVANISED STEEL FRAME
- AUTOMATIC RESET THERMOSTAT CALIBRATED TO 90 °C
- MANUAL RESET THERMOSTAT CALIBRATED TO 100 °C
- NUMBER OF STAGES = 3
Installation, use and maintenance manual
B
C
3000
[kW]
MODEL
3000 5000 7500 10000 12500 15000 20000
Weight (kg)
16
21
D
5000
7500
10000
5
8
12
24
30
33
E
F
12500
15000
16
20
24
36
42
G
20000
32
68