Receipt And Inspection - Mitsubishi Electric s-AIRME-G02 Instructions For Installation, Use And Maintenance Manual

Air-handling units
Table of Contents

Advertisement

4.1.4

Receipt and inspection

Upon receipt, verify the integrity of the machine and check it against the order.
Check the number of packages against the transport document. If incorrect, notify the carrier and the distributor.
Perform a visual inspection of the packaging, when applicable.
Check that the outside of the machine has not been damaged in any way.
Check that the equipment supplied corresponds to the order and the delivery note.
In the event of damage to the product, please provide details in writing and with reserve and send the report to the shipper by
registered mail within 48 hours of delivery (working days). Please also send a copy of the letter to the retailer and the supplier
or distributor. Failure to comply with this procedure will render any claims to the shipper null and void.
If the machine is not installed upon receipt but is put into storage for a long period, set it aside in a protected environment
following the instructions in the chapter 2 "STORAGE".
OBLIGATION:
If any of the packages are damaged or missing, contact the Sales Office of the manufacturer and the
freight forwarder, to agree the next plan of actions.
Technical data plate
The technical data plate (see the example in the chapter 1.2 "Nomenclature") provides the main information needed for electrical
connection of the unit and for proper maintenance. The supply voltage must not exceed +10/-10 %. The power absorbed at full
capacity FLI represents the maximum value that can be reached for the specified operating voltage. The power supply line must
be sized according to the current absorbed by the unit at full capacity, or FLA. The customer must have an adequate power
supply system. It is therefore important to check that the power supply voltage indicated on the rating plate of the unit is
compatible with that of the customer's electrical system.
The data plate also indicates the year of manufacture, model and serial number, the maximum permissible pressures in the
hydraulic circuit, the code of the wiring diagram and the operating weight of the unit.
INFORMATION:
The data on the name plates of s-AIRME-G02/G07 units only refer to such units. For information
regarding Mr. Slim condensing units, refer to the relative documentation.
Identification of the sections
The unit may have been delivered in several sections.
The various sections making up the unit each have a serial number label (see example below) bearing the serial number of the
main unit.
All parts with the same serial number must be assembled to form a single unit.
Installation, use and maintenance manual