be used as an extension. The purpose of the battery temperature sensor is to monitor the
ambient temperature of the batteries over long periods of time and adjust the rectifier output
(float) voltage accordingly. As a result, it is not necessary to have the temperature sensor
touching the batteries. If the Battery Temperature Sensor is removed a "battery temp fault"
alarm is generated.
The "Ambient" temperature sensor (optional) can be used to monitor the temperature in
another location if required. Temperature sensors from the older Sm3x controllers are not
compatible with the EM4x controller.
E
M
6.
NERGY
ANAGER
The energy manager is configured via a web browser-based user interface (Web UI). There are
two methods to access the Web UI:
Ethernet connection from the J305 ethernet connector
Front panel micro-USB local connection
6.1.

Access Levels

There is 1 default access level for the energy manager Web UI from firmware version 10.0:
enaadvanced: this user has normal full control access of the system
The default password = W7h!GJ28KG
There are 3 access levels for the Energy Manager Web UI if upgraded from a version before
10.0:
enaguest
: can only view status of system
enabasic
: reduced privilege, can view settings and system status
enaadvanced : this user has normal full control access of the system
The default password for all levels = ena123
6.2.

Ethernet Port Connection

The energy manager contains static sensitive components that require
careful handling and proper precautions to be taken – an electrostatic
discharge protection device must be worn.
Figure 16: Energy Manager Ethernet Port
Newmar • 1580 Sunflower Ave, Suite 100, Costa Mesa, CA 92626
Phone: 714-751-0488 • E-mail: techservice@Newmarpower.com