NewMar Centurion III C3RS-48-124 Installation & Operation Manual page 19

Table of Contents

Advertisement

Check the Battery Type
The system MUST be
configured to the correct
battery type.
EM4x Web UI page
Battery>Battery Settings
Check/Set Float Voltage
Consult battery manufacturer's data for proper setting.
The Float voltage is for 25°C reference temperature in NewMar systems.
EM4x Web UI page: Control
Example:
Site Setting:
Set Battery Temperature Compensation
Toggle temperature compensation
On.
EM4x Web UI page: Battery>Battery
Settings
You must consult the battery manufacturer's data to obtain the correct Slope setting.
Note that in many Hybrid applications where the battery is constantly being cycled,
having temperature compensation enabled may not be necessary as the voltage on the
battery is constantly changing anyway.
EM4x Web UI page: Battery>Battery Settings
Example:
Site
Settings:
If you choose not to enable Temperature Compensation, then set the Rectifier Float Voltage to
that required by the battery manufacturer for the average long-term temperature you anticipate
your system to operate at.
Set Battery Capacity
Consult the battery manufacturer's data for correct battery capacity settings.
For the EM4x to set the correct Battery Current Limit current, it is essential that this is
filled out correctly. These figures are also used for estimating the Battery Time
Remaining during a discharge.
Newmar • 1580 Sunflower Ave, Suite 100, Costa Mesa, CA 92626
Phone: 714-751-0488 • E-mail: techservice@Newmarpower.com
19
 / 
 / 
 / 

Advertisement

Table of Contents
loading

Table of Contents