6.8.3. Restrictions and Recommendations
• The maximum supported bit rate depends on bus load, bus topology, number of nodes, bus
termination, propagation delay of each CAN node and the bus length.
• Do not connect more than 32 nodes to one CAN network without using a repeater.
• If the bus length exceeds about 200 m, it is recommended to use CAN nodes with built-in galvanic
isolation.
• If the bus length exceeds 1000 m, a CAN bus repeater should be used.
• For additional information refer to the driver documentation for FreeCAN and Can Open in the iX
Developer software.
6.9. USB Flash Drive
The USB port, or ports, are of 2.0 standard and support FAT16, FAT32 and exFAT file systems for USB
flash drives (option, sold separately).
Size limitations for file systems:
• FAT16: up to 2 GB
• FAT32: up to 32 GB
• exFAT: up to 2 TB
Beijer Electronics, MAEN275
23
Additional Installation Tips
2023-09
Need help?