Y16E
Electronic expansion valve (discharge,
cooling or defrost)
Y17E
Electronic expansion valve (discharge,
heating)
Capacity up unit
Notes:
1
This wiring diagram applies only to the capacity up unit.
2
Field wiring
3
Terminal block
Connector
Terminal
Protective earth (screw)
4
S1S is factory set to OFF. Set to ON or REMOTE to operate.
5
Use a voltage-free contact for microcurrent (≤1 mA,
12 V DC). For more information about the remote switches,
see details in
"14.7.1 Low voltage wiring – Capacity up
unit" [ 4  36].
6
Output (caution, warning, run, operation) is 220-240 V AC,
with a maximum load of 0.5 A.
7
For more information about the BS1~BS3 push buttons and
the DS1+DS2 DIP switches, see
settings" [ 4  40].
8
Colours:
BLK
Black
RED
Red
BLU
Blue
WHT
White
GRN
Green
YLW
Yellow
Legend:
A1P
Printed circuit board (main)
A2P
Printed circuit board (M1C)
A3P
Printed circuit board (noise filter) (M1C)
A4P
Printed circuit board (M1F)
A5P
Printed circuit board (ABC I/P 1)
A6P
Printed circuit board (sub)
BS1~BS3
Push buttons (mode, set, return)
C503, C506
Capacitor (A2P)
C507
Film capacitor (A2P)
DS1, DS2
DIP switch (A1P)
E1HC
Crankcase heater (M1C)
F1U, F2U
Fuse (T 6.3 A 250 V) (A1P)
F1U
Fuse (A6P)
F101U
Fuse (A4P)
F3U, F4U
Fuse (B 1 A 250 V)
F401U, F403U
Fuse (A3P)
F601U
Fuse (A2P)
HAP
Light-emitting diode (service monitor is
green) (A1P, A2P, A4P, A6P)
K1R, K2R, K9R~K12R Magnetic relay (A1P)
K3R
Magnetic relay (A2P)
L1R
Reactor (A2P)
M1C
Motor (compressor) (INV1)
M1F
Motor (fan) (FAN1)
PS
Switching power supply (A1P, A2P, A6P)
Q1LD
Earth leakage detector (A1P)
LRYEN10A7Y1+LRNUN5A7Y1
CO₂ Conveni-Pack outdoor unit and capacity up unit
4P605461-1D – 2023.08
"16.1 Making field
R300
Resistor (A2P)
R10
Resistor (current sensor) (A4P)
R1T
Thermistor (air) (A1P)
R2T
Thermistor (M1C suction)
R3T
Thermistor (M1C discharge)
R4T
Thermistor (de-icer)
R5T
Thermistor (liquid separator outlet)
R6T
Thermistor (plate heat exchanger outlet)
R7T
Thermistor (liquid pipe)
R9T
Thermistor (M1C body)
S1NPH
High pressure sensor
S1NPL
Low pressure sensor (air conditioner)
S1NPM
Medium pressure sensor
S1PH
Pressure switch (high pressure protection)
(M1C)
S1S
Operation switch (REMOTE/OFF/ON)
T1A
Current sensor (A1P)
V1R
Power module (A2P, A4P)
V1D
Diode (A2P)
X1A, X2A
Connector (M1F)
X3A
Connector (A1P: X31A)
X4A
Connector (A1P: X32A)
X5A
Connector (A6P: X31A)
X1M
Terminal block (power supply)
X2M
Terminal block
X3M
Terminal block (remote switch)
X4M
Terminal block (compressor)
Y1E
Electronic expansion valve
Y2E
Electronic expansion valve
Y3E
Electronic expansion valve
Y4E
Electronic expansion valve
Z1C~Z11C
Ferrite core
ZF
Noise filter (with surge absorber) (A3P)
19 Technical data