High Voltage Wiring - Capacity Up Unit - Daikin LRYEN10A7Y1 Installation And Operation Manual

Co2 conveni-pack outdoor unit and capacity up unit
Table of Contents

Advertisement

Details – DIII transmission wiring
See
"14.5 Specifications of standard wiring
Details – Remote operation switch
NOTICE
Remote operation switch. The unit is factory-equipped
with an operation switch with which you can turn unit
operation ON/OFF. If you want to remotely turn ON/OFF
operation of the capacity up unit, a remote operation switch
is required. Use a voltage-free contact for microcurrent
(≤1  mA, 12  V  DC). Connect to X3M/1+2 class II
construction, and set to "Remote".
OFF
S1S
S1S
Factory-equipped operation switch:
OFF: Unit operation turned OFF
ON: Unit operation turned ON
Remote: Unit controlled (ON/OFF) with remote operation
switch
Wiring remote operation switch:
Wiring
Maximum wiring length
Details – Remote low noise switch:
NOTICE
Low noise switch. If you want to remotely turn ON/OFF
low noise operation, you must install a low noise switch.
Use a voltage-free contact for microcurrent (≤1  mA,
12 V DC).
Low noise switch
OFF
ON
Wiring low noise switch:
Wiring
Maximum wiring length
LRYEN10A7Y1+LRNUN5A7Y1
CO₂ Conveni-Pack outdoor unit and capacity up unit
4P605461-1D – 2023.08
components" [ 4  34].
Only use harmonised wire
providing double insulation and
suitable for the applicable
voltage.
2-cord cable
0.75~1.25 mm²
130 m
Mode
Normal mode
Low noise mode
Only use harmonised wire
providing double insulation and
suitable for the applicable
voltage.
2-cord cable
0.75~1.25 mm²
130 m
14 Electrical installation
14.7.2
High voltage wiring – Capacity up unit
Connections/routing/fixing
a
b
X2M
c
1
X1M
PE
2
a d/e/f
X1M
Power supply:
a: Power supply cable
b: Overcurrent fuse
c: Earth leakage circuit breaker
PE
Protective earth (screw)
X2M
Output signals:
d: Caution
e: Warning
f: Run
1
X2M
X1M
PE
g
Wiring intake (knockout hole) for high voltage. See
"14.2 Guidelines when knocking out knockout
holes" [ 4  33].
Details – Output signals
NOTICE
Output signals. The outdoor unit is provided with a
terminal (X2M class II construction) that can output 3
different signals. The signal is 220~240  V  AC. The
maximum load for all signals is 0.5  A. The unit outputs a
signal in the following situations:
▪ C/C1: caution signal – connection recommended –
when an error occurs that does not stop unit operation.
▪ C/W1: warning signal – connection recommended –
when an error occurs that causes unit operation to
stop.
▪ R/P2: run signal – connection optional – when the
compressor is running.
Wiring output signals:
X1M
PE
L1 L2 L3
N
L1 L2 L3 N
3N~ 50 Hz
380-415 V
X2M
C C1 W1 R P1 P2
d
e
f
2
g
Installation and operation manual