Specifications

MX Loop Output Reference
Voltage 40 VDC maximum
MX Loop Output
Current 500 mA maximum
Addresses per Loop
4100ES/4100U Panel Capacity
4010ES Panel Capacity
Loop Distance
Loop Resistance
Loop Capacitance
Loop Inductance
Communications Voltage
Module Power Requirements
Module Voltage
Module Input Current
LED Status Indicators (yellow LEDs)
COMM LOSS
EARTH FAULT
Loop Status LED
MX DOWNLOAD
LPS FAULT
4100-5130 or 4010-9916 Voltage Regulator Module
Input Voltage
Input Current
Output Voltage
Output Current
Ripple
Trouble Relay
Mounting Requirements
General Specifications
Mounting
Operating Temperature Range
Operating Humidity Range
Output Wiring Connections
250 Maximum
up to 30, 4100-6077 MX Loop Modules Maximum
Up to 4, 4010-9917 MX Loop Modules Maximum
6560 ft (2000 m) typical maximum
Note: Wire lengths may be longer depending on wiring characteristics and other conditions,
consult your Simplex product representative for additional details
150  maximum
0.2 µF maximum
1.5 mH maximum
40 V peak maximum
24 VDC nominal, supplied from control panel power supply
100 mA for module only (no devices)
1235 mA maximum, fully loaded at 250 devices; actual current depends on connected devices
On steady upon loop communications loss, flashing if not communicating with panel
On steady when an earth fault is detected on field wiring
On steady if no device response
Slow flash if Class A open trouble
Fast flash if short circuit trouble
On steady when module is in service mode and download is in progress
On steady upon loop power supply failure
System supplied 24 VDC
Supervisory = 3 A max. with 2.5 A output load; Alarm = 4.9 A max. with 4 A output load
22.8 to 26.4 VDC (25 VDC nominal); output is resettable, will track state of RESET input
2.5 A maximum supervisory; 4 A maximum alarm
600 mV pk-pk maximum
1 Form C dry contact for monitoring; rated 400 mA @ 30 VDC; changes state for Earth or output
voltage trouble; normally held energized
4 x 5 single block module; requires mounting in same bay as connected power
4100ES/4100U
supply
4010ES
4 x 5 single block module
4" x 10" (102 mm x 254 mm) module requires two vertical 4 x 5 block spaces
32 F to 120 F (0 C to 49 C)
Up to 93% RH, non-condensing @ 90° F (32° C)
On-board terminal blocks for field wiring 18 to 12 AWG (0.82 mm
5
2
2
to 3.31 mm
)
S4100-0059-4, 3/2012