Identifier
Description
TB1
AC supply
TB2
Dual DACT
TB3
Annunciator and auxiliary
power
TB4
Relays
TB5
NAC1 and NAC2
TB6
IDC1 to IDC8
2.2
Power supply specifications
The AC power and battery specifications for the 2008-9101 FACU.
2.2.1
AC power specification
The 2008-9101 FACU operates either on 120 VAC, 60 Hz, 4 A or 240 VAC, 50 Hz, 3 A.
The FACU automatically detects the voltage. You do not require a jumper or switch to select the configuration.
page 7
2008 Foundation Series Fire Alarm Control Unit Installation Guide
Figure 2: 2008-9101 control unit board
Table 1: Description of the main components
Identifier
Description
P1
Battery terminal
P2 and J1
User interface connector
P3
City card connector
P5
Jumper for relay-4 setting
P6
Jumper for relay-3 setting
P7
Jumper for relay-1 setting
Identifier
Description
P8
Jumper for relay-2 setting
P13 to P20
Jumpers for Class A wiring
configuration of IDCs
P21
Jumper for default password
579-1400 Rev B