Replacing A Skylight Actuator - Huawei V500R003C00 Maintenance Manual

Smart modular data center
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Maintenance Guide
Step 8 On the WebUI of the ECC800, choose Monitoring > System > ECC800 > Controls >
Delete device with communication failure, and click Submit.
Step 9 Log in to the ECC800 WebUI, and edit the plan view by adding new devices.
Step 10 Check the parameters and communication status of the AC actuator to ensure normal
communication.
Step 11 Turn on and then turn off the lights to check that the AC actuator supplies power to the lights
properly.
----End

6.4.14 Replacing a Skylight Actuator

Impact on the System
Rotating skylight cannot be controlled.
Preparations
Procedure
Step 1 Label each cable based on the corresponding ports on the skylight actuator.
Step 2 Disconnect cables from the skylight actuator.
Step 3 Remove the failed skylight actuator from guide rails.
Figure 6-50 Removing the skylight actuator
Step 4 Install the reserved skylight actuator in the original position and connect the cables.
Issue 05 (2020-03-25)
Tools: ESD wrist strap, ESD gloves, Phillips screwdriver, step ladder, labels, marker
Material: skylight actuator
Copyright © Huawei Technologies Co., Ltd.
6 Parts Replacement
96