Quarterly Maintenance - Huawei V500R003C00 Maintenance Manual

Smart modular data center
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Maintenance Guide
Item
Check the VCN
indicator.
Check the
ECC800-Pro RUN
indicator (green).
Ambient
temperature
monitoring
Check the indicators
on the iBOX (CIM)
and iBAT (BIM).

4.4 Quarterly Maintenance

Table 4-5 Quarterly maintenance for the power supply and distribution system
Item
Operating
temperature of the
Issue 05 (2020-03-25)
Operation
Observe the
VCN indicator.
Check the RUN
indicator on the
ECC800-Pro
main control
module.
N/A
Visual
observation
Operation
Choose
Monitoring >
Copyright © Huawei Technologies Co., Ltd.
Standard
The VCN indicator is
steady green.
The RUN indicator
blinks at long intervals.
The ambient
temperature of smart
module should be
lower than 45° C.
The RUN indicator
blinks at long
intervals.
The ALM indicator
is off.
Standard
Operating temperature:
4 Routine Maintenance
Troubleshooting
magnetic lock. If not,
replace the magnetic
lock.
For details, see the
VCN related
documents.
If the RUN
indicator blinks at
short intervals,
check whether the
communications
cables are properly
connected between
the ECC800-Pro
and the host.
If the RUN
indicator is off,
rectify any input
grid power fault.
Find the cause of an
abnormal temperature.
If the RUN
indicator blinks at
short intervals,
check whether the
communications
cable is loose or
disconnected. If so,
reconnect the cable.
If the ALM
indicator is steady
on, clear the alarm
by referring to the
iBattery User
Manual.
Troubleshooting
Check whether the data
center smart cooling
24