Prime The Manifold Changeover System. P25 - BeaconMedaes MAT-S Installation, Operation And Maintenance Instructions

Medical gas supply system cylinder manifold system and manifold changeover system
Table of Contents

Advertisement

Medical Gas Supply System
Table 4: Default Line Pressure Alarm Settings.
Nominal
Line
Low Pressure
Pressure
Alarm
55 psi
100 psi
180 psi
3.4.13 The controller screen output alarm conditions
will show as per Figure 23.
Figure 23 - Low Line Pressure Fault.
1500
150
PSI
3.4.14 Adjust the line pressure back to nominal (see
Table 5 in Section 4, principles of operation for typical
line pressure settings). The controller screen and output
alarm conditions will change typically as shown in Figure
16.
3.4.15 Close off the slow bleed from the vent valve.
3.4.16 Close all bank cylinder valves.
3.5
Prime the Manifold Changeover
System.
3.5.1
Complete the steps in Section 4.2 - Procedure to
prime Manifold Changeover System, to bring it online.
Default Values
High Pressure
Alarm
44
66
80
120
144
216
O2
1500
SCFH
40
1500
44.0
66.0
150
PSI
PSI
110.0
25
4109992459.00