Electrical Work; Power Supply For Outdoor Unit - Mitsubishi Electric HYBRID CITY MULTI PURY-M200-300YNW-A Data Book

Table of Contents

Advertisement

9. ELECTRICAL WORK

9-1. Power supply for Outdoor unit

9. ELECTRICAL WORK
9-1-1. Electrical characteristics of the outdoor unit in cooling mode
PURY-M-YNW-A
PURY-M200YNW-A(-BS)
PURY-M250YNW-A(-BS)
PURY-M300YNW-A(-BS)
PURY-EM-YNW-A
PURY-EM200YNW-A(-BS)
PURY-EM250YNW-A(-BS)
PURY-EM300YNW-A(-BS)
MEES17K104
Units
Unit Combination
Hz
Volts
-
380
-
50/60
400
415
-
Units
Unit Combination
Hz
Volts
-
380
-
50/60
400
415
-
Symbols: MCA: Max Circuit Amps
RLA: Rated Load Amps
Power
Compressor
supply
Voltage
Output
MCA(A)
SC(A) Output(kW)
range
(kW)
16.1
6.0
8
Max:456V
20.4
7.5
8
Min:342V
25.1
8.5
8
Power
Compressor
supply
Voltage
Output
MCA(A)
SC(A) Output(kW)
range
(kW)
16.1
6.0
8
Max:456V
19.8
7.5
8
Min:342V
23.4
8.5
8
R2-Series
SC: Starting Current
FAN
RLA(A)(50/60Hz)
Cooling
Heating
0.92
11.5/10.9/10.5 11.7/11.1/10.7
0.92
16.7/15.9/15.3 16.9/16.1/15.5
0.92
18.7/17.7/17.1 19.7/18.7/18.0
FAN
RLA(A)(50/60Hz)
Cooling
Heating
0.92
10.3/9.8/9.5
11.4/10.8/10.4
0.92
14.8/14.0/13.5 16.6/15.7/15.2
0.92
16.9/16.0/15.4 18.4/17.4/16.8
33