9. Troubleshooting

If the air heater malfunctions, first check if the problem is
caused by external circumstances (e.g. no supply power).
If the problem is not caused by external circumstances,
use the tables and instructions in this chapter to fix the air
heater.
NOTICE
Please remember the built in waiting times of
the air heater; the signals of the LED's and the code on the
display. Do not react too soon.
The error codes below, refer to the gas booster of the
hybrid air heater. The error codes of the connected heat
pump are visible in the Smart Controller too. Consult the
manual of the heat pump for details.

9.1. Volatile lock outs

The table below describes the volatile lock outs that can
occur. These can only be reset by hand.
Display
Error type
L-0
Internal error
L-1
Ignition error
L-2 and 3
Internal error
L-4
E-error
L-5
Burner fan error
L-6 and 7
Burner fan error
L-8 to 12
Internal error
L-13
Pressure switch error Pressure switch is closed
L-14
Pressure switch error Pressure switch does not
L-15
Overheating
L-16
Flue temperature
error
L-17 to 19 Internal error
L-20
Flame error
L-21
Flame error
L-22
Flame error
L-25
Sensor error
L-26
Sensor error
L-27 to 31 Internal error
INSTALLATION MANUAL AIR HEATER TYPE QSG
Description
Case #
Internal error
13
Flame lasts only 5
1
seconds after ignition
No flame after ignition
2
Internal error
13
E-error for more than 24
12
hours
Burner fan does not work
6
Burner fan rotates at the
7
wrong speed
Internal error
13
14
in stand-by mode
11
close during pre-purge
Heat exchange sensor is
3
overheated
Flue sensor is overheated
3
Internal error
13
Flame detected after
15
closing the gas valve
Flame detected before
16
opening the gas valve.
Flame failure during
5
burning
Heat exchange sensor
4
failure
Flue sensor failure
4
Internal error
13
Display
Error type
L-32
Sensor error
L-33 to 38 Internal error
L-42
Flue temperature
error
L-43
Overheating

9.2. Temporary errors

The table below describes the temporary errors that can
occur. These will disappear automatically after the cause
has been resolved.
Display
Error type
E-00 to 04
Internal error
E-05
Overheating
E-06 to 13
Internal error
E-14
Flame error
E-15 to 19
Internal error
E-20 and 21
Heat exchanger
sensor error
E-22
Internal error
E-23 and 24
Flue sensor error Flue sensor not detected
E-27 and 28
Heat exchanger
sensor error
E-30 and 31
Flue sensor error Flue sensor short-circuit
E-34
Reset button
error
E-36
Overheating
E-38 and 39
Heat exchanger
sensor error
E-47 and 48
Heat exchanger
sensor error
E-49 to 64
Internal error
E-65
Voltage too low
E-66
Voltage too high
E-67
Pressure switch
error
E-68
Flue
temperature
error
E-69
Configuration
error
Description
Case #
Heat exchange sensor
4
failure
Internal error
13
Too many flue
3
temperature errors
Heat exchange sensor is
3
overheated too often
Description
Case #
Internal error
13
Heat exchange sensor is
3
overheated
Internal error
13
Flame detected when
16
there shouldn't be one
Internal error
13
Heat exchanger sensor
4
not detected
Internal error
13
4
Heat exchanger sensor
4
short-circuit
4
Too many reset actions in
9
a short timespan
Heat exchange sensor is
3
overheated
Heat exchanger sensor
4
not detected
Heat exchange sensor
4
short-circuit
Internal error
13
Supply voltage is too low
for over 1 minute
Supply voltage is too high
for over 1 minute
Too many pressure switch
11
errors
Flue sensor is overheated
3
Heater configuration error 19