Fault code Table
Table. 8- List of faults
Fault code Fault
A01
No burner ignition
A02
Flame signal present with burner off
A05
Fan fault
A06
No flame after the ignition phase
F07 - F14 -
High flue gas temperature
A07
F08
Over temperature protection inter-
A08
vention
F09
Over temperature protection inter-
A09
vention
F10
Flow sensor fault
A10
F11
Return sensor fault
A11
F12
DHW sensor fault
F13
Flue probe fault
A13
40
BLUEHELIX PRO RRT 24 C
Possible cause
No gas
Ignition/detection electrode fault
Faulty gas valve
Insufficient gas supply pressure
Condense trap or pipes blocked
Air/fume ducts obstructed
Electrode fault
PCB fault
No 230V power supply
Tachometric signal interrupted
Fan damaged or out of balance
Ionisation electrode fault
Flame unstable
air/flue ducts obstructed
Condense trap or pipes blocked
The flue gas probe detects an exces-
sive temperature
Heating sensor damaged
No water circulation in the system
Air in the system
Return sensor damaged
No water circulation in the system
Air in the system
Sensor damaged
Wiring shorted
Wiring disconnected
Sensor damaged
Wiring shorted
Wiring disconnected
Sensor damaged
Wiring shorted
Wiring disconnected
Probe damaged
Wiring shorted
Wiring disconnected
cod. 3541T010 - Rev. 00 - 10/2019
Cure
Check for correct gas flow & pressure to the
boiler and that the pipework has been purged.
Check the wiring of the electrode and that it is
correctly positioned and free of any deposits;
replace / clean the electrode if necessary.
Check the gas valve and replace it if necessary
Check the gas supply pressure
Check the trap and pipes, clean it if necessary
Remove the obstruction from the flue, extraction
ducts, air inlet and terminals.
Check the ionisation electrode wiring
Check the condition of the electrode
Electrode to earth
Cable to earth
Check the condenser trap clean it if necessary
Check the PCB
Check the 5-pin connector wiring
Check the fan, clean or replace
Check the position of the ionisation electrode and
replace it if necessary
Check the burner
Remove the obstruction from the flue, fume
extraction ducts, air inlet and terminals
Check the trap and pipes clean it if necessary
Check the exchanger
Check the flue gas probe
Check the correct positioning and operation of
the heating sensor and replace it if necessary
Check the circulating pump
Vent the system
Check the correct positioning and operation of
the return sensor and replace it if necessary
Check the circulating pump
Vent the system
Check the wiring or replace the sensor
Check the wiring or replace the sensor
Check the wiring or replace the sensor
Check the wiring or replace the flue probe