Procedure for modifying parameter SC12:
Create a demand for heating or DHW and then press the reset button (ref. 6 fig. 1) for 10 seconds.
The display shows 100 and the text "Co" flashing; press the "Heating +" button (ref. 4 fig. 1) until 120 is displayed.
Then press the "DHW +" button (ref. 2 fig. 1) until the access code 123 is displayed.
Press the reset button (ref. 6 fig. 1) once.
The display shows Ts flashing; press the "heating +" button (ref. 4 fig. 1) once.
The display shows Sc flashing; press the reset button once.
The display shows Sc alternating with 01 flashing;
Press the "heating +" button (ref. 4 fig. 1) until displaying Sc alternately with 15 flashing;
Press the "DHW +" button and the display shows "00";
Press the "DHW +" button until the display shows "02";
Press the "heating +" button (ref. 4 fig. 1) to confirm and the 100% calibration mode will activate displaying the mes-
sage "CA" and "LI" alternating.
after just over a minute the calibration mode will end and the display will show "C" alternating with "12" with the con-
tinuous flame symbol.
press the "DHW +" or "DHW -" button to set the "SC12" parameter value to the value that allows CO
press the "heating +" button to confirm the value. The display shows "Sc" alternating with "15".
Press the Reset button to return to the Service Menu. Press the Reset button for 10 seconds to exit the PCB Service
Menu, or exiting occurs automatically after 15 minutes
put the boiler in TEST mode and check the CO
flue gas analyser.
Procedure for modifying parameters SC12 and SC13:
Create a demand for heating or DHW and then press the Reset button (ref. 6 fig. 1) for 10 seconds.
The display shows 100 and the text "Co" flashing; press the "Heating +" button (ref. 4 fig. 1) until 120 is displayed.
Then press the "DHW +" button (ref. 2 fig. 1) until the access code 123 is displayed.
Press the Reset button (ref. 6 fig. 1) once.
The display shows Ts flashing; press the "heating +" button (ref. 4 fig. 1) once.
The display shows Sc flashing; press the reset button once.
The display shows Sc alternating with 01 flashing;
Press the "heating +" button (ref. 4 fig. 1) until displaying Sc alternately with 15 flashing;
Press the "DHW +" button and the display shows "00";
Press the "DHW +" button until the display shows "03";
Press the "heating +" button (ref. 4 fig. 1) to confirm and the 100% calibration mode will activate displaying the mes-
sage "CA" and "LI" alternating.
after just over a minute the calibration mode will end and the display will show "C" alternating with "12" with the con-
tinuous flame symbol.
press the "DHW +" or "DHW -" button to set the "SC12" parameter value to the value that allows CO
press the "heating +" button to confirm the value. The display shows "CA" and "LI" alternately to indicate that a fur-
ther calibration is being performed.
after just over a minute the calibration mode will end and the display will show "C" alternating with "15" with the con-
tinuous flame symbol.
press the "DHW +" or "DHW -" button to set the "SC13" parameter value to the value that allows CO
press the "heating +" button to confirm the value. The display "SC" appears alternately to "15".
Press the Reset button to return to the Service Menu. Press the Reset button for 10 seconds to exit the PCB Service
Menu, or exiting occurs automatically after 15 minutes
put the boiler in TEST mode and check the CO
flue gas analyser.
28
BLUEHELIX PRO RRT 24 C
value at maximum and minimum power with a calibrated electronic
2
value at maximum and minimum power with a calibrated electronic
2
cod. 3541T010 - Rev. 00 - 10/2019
optimisation.
2
optimisation.
2
optimisation.
2
EN