BLUEHELIX PRO RRT 24 C
Circulating pump
Before carrying out the following instructions it is advisable to protect the area and the boiler's PCB housing
A
against accidental water spillage.
1
2
fig. 38
Isolate the power supply and close the Gas isolation valve to the boiler.
Pull up the security tab "1" of fig. 38 then remove both electrical connections to the pump "2".
Close the flow & return Isolation valves, & drain the water in the boiler "3" of fig. 39 " (see "System draining" on
page 8).
Unscrew ( 4 x 5mm Allen key bolts) and remove the circulating pump motor assembly of fig. 40 .
Replace in reverse order, refill the boiler, re-establish the power supply & test
EN
fig. 39
cod. 3541T010 - Rev. 00 - 10/2019
fig. 40
33