Contents Description
b21
PVC flue maximum temperature
b22
CPVC flue maximum temperature
b23
Standard flue shutdown maximum temperature
b24
PVC flue shutdown maximum temperature
b25
CPVC flue shutdown maximum temperature
b26
Flow temperature limit in automatic calibration
Maximum temperature during calibration in DHW
b27
mode
b28
Flowmeter sensitivity factor
b29
Restoring Factory Values
P30
Heating ramp rate
P31
Virtual setpoint min. temperature
P32
Heating standby time
P33
Heating Post-Circulation
P34
Pump operation
P35
Modulating pump min. speed
P36
Modulating pump start speed
P37
Modulating pump max. speed
Pump deactivation temperature during Post-Circu-
P38
lation
Pump activation hysteresis temperature during
P39
Post-Circulation
P40
Heating user max. setpoint
P41
Max. output in heating
P42
Burner shutdown in DHW
P43
Comfort activation temperature
P44
Not used
P45
DHW standby time
P46
DHW user max. setpoint
P47
DHW pump Post-Circulation
P48
Max. output in DHW
P49
Comfort1 standby time
P50
Comfort2 standby time
P51
Solar deactivation temperature
P52
Solar ignition temperature
P53
Solar standby time
Heating T temperature adjustment
P54
P55
Primary exchanger protection temperature
P56
System min. pressure value
P57
System nominal pressure value
P58
Exchanger protection intervention
P59
Heating hysteresis after ignition
P60
Timer for heating hysteresis after ignition
P61
Pump deactivation with Open Therm
Notes:
1. Parameters with more than one description vary their function and/or range in relation to the setting of the parameter given in
brackets.
2. Parameters with more than one description are reset to the default value if the parameter given in brackets is modified.
3. The Maximum Heating Power parameter can also be modified in Test Mode.
Press the Reset button to return to the Service Menu. Press the Reset button for 20 seconds to exit the PCB Service Menu, or exiting
occurs automatically after 15 minutes.
26
BLUEHELIX PRO RRT 24 C
Range
60÷110°C
60÷110°C
60÷110°C
60÷110°C
60÷110°C
25°C ÷ 55°C
75°C ÷ 95°C
0 ÷ 60 (0 = disabled)
Change the value from 0 to 10 by pressing the "DHW +"
button. Confirm by pressing the "heating +" button.
1÷20°C/minute
0 = Deactivated
1÷80°C
0÷10 minutes
0÷255 minutes
0÷3 = Operation strategy
30-100%
90-100%
90-100%
0÷100°C
0÷100°C
20÷90°C
0÷100%
0 = Fixed
1 = Linked to setpoint
2 = Solar
0÷50°C
Do not modify
30÷255 seconds
40÷70°C
0÷255 seconds
0÷100%
0÷100 minutes
0÷100 minutes
0÷100°C
0÷100°C
0÷255 seconds
0÷60°C
0÷150°C
0÷8 bar/10 (Only for boilers with water pressure sensor) 4 bar/10
5÷20 bar/10 (Only for boilers with water pressure sen-
sor)
0 = No F43
1-15=1-15°C/second
6÷30°C
60÷180 seconds
0-1
cod. 3541T010 - Rev. 00 - 10/2019
Default
88°C
93°C
100°C
93°C
98°C
30°C
80°C
20
-
4°C/minute
0
4
15
2
30%
90%
100%
50°C
10°C
80°C
80%
0
40°C
0
60
55°C
50
100%
20
42
10°C
10°C
10
18°C
43°C
7 bar/10
10°C/second
10°C
60
0