CAUTION: Electrostatic discharge can damage electronic components. Be sure you are properly grounded before
beginning this procedure.
CAUTION: Failure to properly handle HPE Persistent Memory modules can damage the component and the
system board connector.
2.
Power down the server.
3.
Remove all power:
a. Disconnect each power cord from the power source.
b. Disconnect each power cord from the server.
4.
Do one of the following:
Extend the server from the rack (Extending the server from the rack).
Remove the server from the rack (Removing the server from the rack).
5.
Place the server on a flat, level work surface.
6.
Remove the access panel (Removing the access panel).
CAUTION: Do not operate the server for long periods with the access panel open or removed. Operating the server
in this manner results in improper airflow and improper cooling that can lead to thermal damage.
7.
Remove the primary PCIe riser cage (Removing a primary PCIe riser cage).
8.
If installed, remove the butterfly riser cage (Removing a butterfly PCIe riser cage).
9.
Remove the air baffle (Removing the air baffle).
10. If installed, remove the processor mezzanine tray (Removing and replacing the processor mezzanine tray).
11. Remove the HPE Persistent Memory module.
12. Install the new HPE Persistent Memory module, and review the persistent memory configuration of the server.
58
Removal and replacement procedures