18 EN – Quick installation and start-up guide
Connection
XDI Digital inputs
EN
DA
DE
X12
ES
X13
X205
FI
The wire size accepted by all screw connectors (for both stranded and solid wire) is
FR
2
0.5 ... 2.5 mm
IT
Remove the cardboard covers
NL
After the electrical installation has been done and there is no danger of dropping
screws or anything else inside the drive or LCL filter module, remove the cardboard
PL
covers from the top of them. See
PT
covers (Page
299).
SV
Start-up the drive
TR
Before you start up the drive, make sure that the installation is completed.
Make sure also that it is safe to start the motor. Disconnect the motor from
ZH
other machinery if there is a risk of damage or injury.
Before you activate the automatic fault reset or automatic restart functions
of the drive control program, make sure that no dangerous situations can
occur. These functions reset the drive automatically and continue operation
after a fault or supply break. If these functions are activated, the installation
must be clearly marked as defined in IEC/EN/UL 61800-5-1, subclause 6.5.3,
for example, "THIS MACHINE STARTS AUTOMATICALLY".
Use the control panel to do the start-up procedure. The two commands at the bottom
of the display show the functions of the two softkeys
display. The commands assigned to the softkeys are different depending on the
context. Use the arrow keys
depending on the active view. Key
Term
+24VD
1
DI1
2
DI2
3
DI3
4
DI4
5
DI5
6
DI6
OUT
1
SGND
SGND
2
3
IN1
4
IN2
Safety options connection
Control panel connection
Memory unit connection
(24...12 AWG). The torque is 0.5 N·m (5 lbf·in).
Installing the air baffles and removing the cardboard
,
,
?
DI1
Stop (0) / Start (1)
DI2
Forward (0) / Reverse (1)
DI3
Reset
DI4
Acc/Dec time select
DI5
Constant speed 1 (1 = On)
DI6
By default, not in use.
OUT
Safe torque off circuits must be closed for the
drive to start.
IN1
IN2
and
and
to move the cursor or change values
shows a context-sensitive help page.
Description
located below the

Advertisement

Table of Contents
loading

Table of Contents