Self testing maintained emergency luminaire

Advertisement

emergency mode is at least the one that is
stated in the list of the first page. During
emergency mode, a LED strip test is also
performed.
Resetting Errors
Push the Test button for 5 seconds, to
extinguish all the indicated LED errors. Then
the luminaire enters regular operation mode.
Indication LED status (with connected
mains power supply).
AC Charge
On:
Good charge current.
Οff:
No battery (No charging current
or disconnected battery).
Lamp fault
Οn:
Off:
Fault
Οff:
Blink (With AC Charge LED ON): Autonomy or
low battery problem
(the battery must be replaced).
Blink (With AC Charge LED Off):
No charging current or disconnected battery.
Mounting methods
All luminaires, can be mounted either surface or in
suspended ceilings.
Suspended ceiling installation.
On the bottom of the base plastic of the luminaire there
are two H shaped cut outs. These are used to install
the A-3018 mounting springs.
1. With a sharp tool remove the appropriate plastic
pieces to fit the mounting springs. First place the edges
of the mounting spring to the respective holes and
install the one end of the coil to the support axis.
2. Install the other end of the coil to the other support
axis.
3. Bend the springs and place the luminaire to the
respective suspended ceiling's hole.
The luminaire's placement to the suspended ceiling
must be done after the connection with power supply
cables.
Page 2 from 5
faulty LED strip.
Good LED strip.
Battery OK.
ΑΤΤΕΝΤΙΟΝ!!!
1. Operations for installation, maintainance or
testing must be done by authorized personel
only.
2. The device must be connected to the mains
power supply thru a fuse dependent by the total
amount of the line's power load.
3 .
I n c a s e o f b a t t e r y o r l i g h t s o u r c e
replacement, these must be replaced by parts of
the same type, by the manufacturer or by a
competent person.
4. In case of inactive use for a period greater
than 2 months, disconnect the battery by pulling
out the battery's connector.
5. I s not allowed to discard batteries in to
t i
common trash bins, they must be
discarded only
points. Do not incinerate.
Α-3018 mounting springs
Mounting the luminaire
Required
opening in
a suspended
ceiling
in battery recycling
1
2
3
Suspended ceiling
in a suspended ceiling
260
923427000_09_005
110

Advertisement