Initiating The "Test" Sequence; Resetting The Controller To Factory Defaults - Dantherm iA/C T-A6000, iA/C T-B6000, iA/C T-B8000 Product Information Manual

Table of Contents

Advertisement

iA/C T-Series Installation, Operating & Maintenance Manual

Initiating the "TEST" sequence

5.5.2
1. Press L button for 2 seconds and release (Display will begin "Display Mode")
2. Press L&R button simultaneously for 2 seconds and release (Display will show "test")
3. Press L button for 2 seconds and release (Display will show test step)
4. TEST steps
STEP
0
1
2
3
4
5
6
5.5.3

Resetting the controller to factory defaults

1.
Ensure return temperature is displayed otherwise wait 30 seconds
Press L&R button for 15 seconds and release (Display will show "----")
2.
AC-6 iAC 6K 8K Manual Rev B
DESCRIPTION
Display S/W Revision Level
Int. Fan only
Heater
Int. Fan only
Con Fan
Comp. and cond.
Int. Fan only
INT.
LED
HEATER
FAN
X.XX
ON
OFF
T01
ON
OFF
T02
ON
ON
T03
ON
OFF
T04
ON
OFF
T04
ON
OFF
T05
ON
OFF
COND.
COMP
DURATION
FAN
OFF
OFF
10 SEC
OFF
OFF
30 SEC
OFF
OFF
35 SEC
OFF
OFF
20 SEC
OFF
Cycle
30 SEC
ON
ON
75 SEC
OFF
OFF
30 SEC
Page 12 of 22

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ia/c t series

Table of Contents