产 品 使 用 产 品 使 用 The DC Air Conditioner 450 is especially designed for cooling of electronic equipment and for in and out door installation. The unit must not be used for other purposes under any condition and should be installed and placed according to the instructions in this manual.
符 合 性 声 明 符 合 性 声 明 符 合 性 声 明 Dantherm declares, meet 2002/95/EC.ROHS directive for mass production. This unit is in conform- ity with the following directives and standards 2002/95/EC.ROHS ( ( ( (...
2.2 Contents in the package 包 装 内 容 包 装 内 容 包 装 内 容 包 装 内 容 The DC Air Conditioner 450 is delivered with an installation kit with the following contents: Item description Quantity Unit DC Air Conditioner 450/ Pcs.
2.4 Mounting Mounting procedure The mounting procedure of the air conditioner unit should follow below steps: Demount the package. Install the water tube, fasten with a cable tie, and cut the extra part. Lift the unit up and place it in the wall of cabinet, fasten the brackets and flanges with M6 bolts &...
机器的识别 All units have a silver type plate label, where all the important information about the specific unit can be found. Also the Dantherm address and phone numbers are printed here so the contact can be made on the site.
4 Description of functionality 功能描述 功能描述 功能描述 功能描述 4.1 General Description The air conditioner contains a compressor, evaporator, condenser, condenser fans, and various cooling components as expansion valves, dry filter and an internal fan. The internal cabinet air is continuously circulated in a closed loop by the evaporator fan. This draws warm air from the top cabinet and supplies the internal environment with cooled air in the bottom area via the evaporator coil.
Exhaust air temperature 排 风 温 度 Return air temperature 回 风 温 度 Supply air temperature 送 风 温 度 Ambient air temperature 环 境 空 气 4.3 Set points The set points can be adjusted through controller software. The table below shows the set point related information.
Standard Range Unit Description Function settings If the return air Temp. exceeds set Temp and the compressor starts running. Compressor start-up set Temp. [20-40] °C The compressor stops when the return air Temp is lower 3°C than set Temp. (default 22°C). 3°C 22°C 4.4 Compressor operation...
6 Preventive maintenance 定期维护 定期维护 定期维护 定期维护 6.1 General Description This heat management system contains moving mechanical parts, and is often placed in rough environments with high temperatures, humidity and dirt. To keep the air conditioner in a shape where it will perform according to the specifications, preventive maintenance has to be carried out. Warning Do not start working on the unit before the power is safely switched off.
6.2 Clean-up methods Make sure that the power to the unit is safely switched off. clean-up method Needed Tools and materials Vacuum cleaner or compressed air Mechanical cleaning Soft bristle brush Screwdriver NHR-60 cleaning agent for coil’s fins Liquid cleaning Screwdriver Water Mechanical Cleaning recommended cleaning method...
Page 15
Liquid Cleaning Step Action Open the units cover, use CNHR-60 cleaning agent sprayed evenly on the surface of the condenser and evaporator fins, condenser fan, air duct; five minutes later, then use the low pressure water to rinse them. CNHR-60 Finish all the items in the below check list.
6.3 Check list Checklist Are the fans clean and free of corrosion? Are the coolant pipes free of obstructions, damage, corrosion and show no obvious signs of leakage? Are the coil lamellas clean and undamaged? Are all fan blades free of obstructions, cracks, missing blades and in balance? Do the fans rotate freely and are they free from excessive vibration or noise?
– so only replace if the compo- nent is faulty! Before demounting the old part, it is very important to order the new spare part from Dantherm. To do this most effectively, the product version and serial number should be checked so this infor- mation can be passed on when ordering.
Page 18
4-Serrated washer and nut 齿 垫 和 螺 母 Step Action 行 动 行 动 行 动 行 动 步 骤 步 骤 步 骤 步 骤 Power off and Uninstall A/C from the cabinet. 断 电 并 将 空 调 从 机 柜 上 卸 下 。 Trim the cable tie mounting the sensor on internal cover grid, remove 8 hexagon lobular socket countersunk head bolts mounting the internal cover and unplug the cable con- necter.
8 Scrapping 报废 报废 报废 报废 Main components 主 要 部 件 主 要 部 件 主 要 部 件 主 要 部 件 The main components of the unit are: The cooling circuit including the compressor, coils and refrigerant liquid. The printed circuit boards (PCB’s) with electronic components and connecting wires Fans Metal parts such as shell...
10 spare parts list 备件清单 备件清单 备件清单 备件清单 If you want to replace the spare parts , p lease accorded to the following table and contact with service to purchase. 如 果 您 需 要 更 换 备 件 , 请 按 照 下 表 联 系 丹 腾 售 后 进 行 采 购 。 NO.
12 Hotline helps 热线帮助 热线帮助 热线帮助 热线帮助 The service department of Dantherm is ready to help in case of a problem. Please help yourself and us by having the following information’s prepared before making the call. Your name: Company name:...