Fig. 3 Class B, Hnet/Xnet Wiring On Nic-C - Siemens FN2013-U1 Installation Manual

Fiber network module
Table of Contents

Advertisement

Pin
Designation
NIC-C/1
-
NIC-C/2
+
NIC-C/3-24
NC
EF1/A1
+
EF1/B1
-
Power A/+
+
Power A/-
-
Power B
NC
A6V12093642_en--_b
Wiring class B HNET/XNET on NIC-C
[1]
_
NC
+
1
2
3
4
5
9
10
11
12
13
NC
NIC-C
ONE SLOT OF CC-5/CC-2
17
18
19
20
21
NC
Fig. 3: Class B, HNET/XNET wiring on NIC-C
Description
NIC-C,RS48 circuit 1 -, monitored by NIC-C
NIC-C, RS48 circuit 1 +, monitored by NIC-C
NIC-C, do not use
Fiber network module, RS485 circuit 1 +
Fiber network module, RS485 circuit 1 -
Fiber network module, + DC 24 V
Fiber network module, GND
Fiber network module, do not use
1
RS485 ratings:
- 8 V P-P, 150 mA max.,
- 2000 ft/610 m max
- 16 AWG max., 18 AWG min.,
- Positive or negative ground fault supervision at < 10 kΩ
2
Only connect to a UL864/ULC-S527 approved, power-limited, and regulated power
unit, e.g., PSC-12 / PSC-12M (TB3).
No EOL resistor required on NIC-C or fiber network module.
2023-01-23
Fiber network module FN2013 / FN2014
6
7
8
14
15
16
22
23
24
1
1
2
2
Wiring
FN2013 / FN2014
+
A1
Line 1
EF1
NC
_
B1
SIEMENS
A2
Line 2
EF2
NC
B2
Power A
Power B
-
NC
NC
NC
NC
NC NC
[2]
DC 24 V
1
Rx
Tx
Rx
Tx
NC
NC
9 | 28

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fn2014-u1

Table of Contents