Mitsubishi MELSEC-Q Q68TD-G-H02 User Manual page 11

Channel isolated thermocouple input module
Hide thumbs Also See for MELSEC-Q Q68TD-G-H02:
Table of Contents

Advertisement

(2) Usable Thermocouples and Conversion Accuracies
The following table explains the usable thermocouples and
conversion accuracies.
Table2.2 Usable thermocouples and conversion accuracies
Usable
Measured Temperature
Thermo couple
Range*1
Type
0 to 600
600 to 800
B
800 to 1700
1700 to 1820
-50 to 0
0 to 300
R
300 to 1600
1600 to 1760
-50 to 0
0 to 300
S
300 to 1600
1600 to 1760
-270 to -200
-200 to 0
K
0 to 1200
1200 to 1370
-270 to -200
-200 to 0
E
0 to 900
900 to 1000
-210 to -40
J
-40 to 750
750 to 1200
-270 to -200
-200 to 0
T
0 to 350
350 to 400
-270 to -200
-200 to 0
N
0 to 1250
1250 to 1300
*1 If a value entered from the thermocouple is outside the measured temperature range given in the table, it is
handled as the maximum/minimum value of the measured temperature range.
*2 The accuracies only in the temperature ranges of Class 1 to 3 (shaded areas) in JIS C1602-1995 apply.
Q68TD-G-H02 needs to be powered on 30 minutes prior to operation for compliance to the specification
(accuracy).
*3 Temperature measurement can be executed, but accuracy is not guaranteed.
Conversion Accuracy
(At operating ambient temperature
25
5
----- *3
*2
3.0
*2
2.5
----- *3
----- *3
*2
2.5
*2
2.0
----- *3
----- *3
*2
2.5
*2
2.0
----- *3
----- *3
Larger value of
*2
0.5% of measured temperature
Larger value of
*2
0.5% of measured temperature
----- *3
----- *3
Larger value of
*2
0.5% of measured temperature
Larger value of
*2
0.25% of measured temperature
----- *3
----- *3
Larger value of
*2
0.25% of measured temperature
----- *3
----- *3
Larger value of
*2
0.5% of measured temperature
Larger value of
*2
0.25% of measured temperature
----- *3
----- *3
Larger value of
*2
0.5% of measured temperature
Larger value of
*2
0.25% of measured temperature
----- *3
Temperature Characteristic
(Per operating ambient
)
temperature variation of 1
0.5
and
Larger value of
0.2% of measured temperature
0.25
and
Larger value of
0.02% of measured temperature
0.5
and
Larger value of
0.15% of measured temperature
0.5
and
Larger value of
0.02% of measured temperature
0.5
and
Larger value of
0.02% of measured temperature
0.5
and
Larger value of
0.1% of measured temperature
0.5
and
Larger value of
0.02% of measured temperature
0.5
and
Larger value of
0.2% of measured temperature
0.5
and
Larger value of
0.02% of measured temperature
4
Max. Temperature
Error at Ambient
)
Temperature 55
----- *3
0.4
----- *3
----- *3
0.4
0.3
----- *3
----- *3
0.4
0.3
----- *3
----- *3
0.06
and
0.06
and
----- *3
----- *3
0.06
and
0.06
and
----- *3
----- *3
0.06
and
----- *3
----- *3
0.06
and
0.06
and
----- *3
----- *3
0.06
and
0.06
and
----- *3
----- *3
13.0
12.5
----- *3
----- *3
12.5
9.5
----- *3
----- *3
12.5
9.5
----- *3
----- *3
11.0
9.0
----- *3
----- *3
8.5
6.75
----- *3
----- *3
5.625
----- *3
----- *3
6.0
2.625
----- *3
----- *3
11.0
9.375
----- *3