D. Connecting to SLP
Terminating horizontally is not allowed.
Vertical terminations are measured to top of chimney.
Flex
Min SLP
5 ft.
8 ft.
6 ft.
7 ft.
7 ft.
6 ft.
8 ft.
5 ft.
9 ft.
4 ft.
10 ft.
N/A
NOTE: 3 in. sections
of flex pipe must be
enclosed to existing
masonry fireplace flue
vent or installed into an
existing wood burning
vent system.
Four 45 degree elbows can be used in the vertical section of SLP venting to avoid structural members such as
floor joist or trusses. Maximum total vent run is 50 ft. 90 degree elbows may NOT be used.
Up to four 45 degree elbows may be used as long as the minimum venting requirements are met per the above
chart.
Figure 5.5 Optional SLP Venting Configuration - Vertical Termination
Heat & Glo • COSMO-I30-IFT, COSMO-I35-IFT Installation Manual • 2535-980 Rev. V • 10/23
24
SLP
INLET AIR
VENT PIPE
3 in
Flex
This appliance is listed for use with LINK-DV systems
and components only. It is permissible to extend venting
above existing chimney (within specified maximum ver-
tical limits) using SLP series 6-5/8 inch gas direct-vent
pipe. Connection is made using DV-46DVA-GK.
SLP-TVHW
Must adhere to pipe clearances.
SLP 6-5/8 Ø
COLINEAR TO COAXIAL
ADAPTER DV-46DVA-GK
EXHAUST AIR VENT PIPE
FLEXIBLE FLUE
LINK-DV30B/LINKSQ-DV30: This installation
may perform better and allow less cold air in-
filtration in negative pressure settings.
LINK-DV430B/LINKSQ-DV4-30:
• This installation may be more susceptible to
cold air infiltration and the effects of negative
pressure on the appliance's performance.
• Depending on the chimney cleanliness,
consider using the full length intake so
as to lessen the possibility of sense rod
contamination and flame rectification
issues.