Danfoss EIM 365 User Manual page 18

Superheat controller
Table of Contents

Advertisement

Superheat controller, type EIM 365 (PV01)
Sensor, Valve and Refrigerant Configuration
Pressure Sensor Settings
The pressure sensor input is setup by default to accept an AKS32R pressure transducer. If another sensor is to be
used, it is important to note that it needs to be a 0.5 - 4.5 Vd.c. radiometric type (10% - 90% of supply voltage). The
default range for the sensor is 0 to 16 bar absolute. This can be changed by setting the minimum transducer
pressure "o20 MinTransPres" and the maximum transducer pressure "o21 MaxTransPres" to the new values. The
values must be entered in bar absolute so a sensor with a range of -1 to 12 bar gauge, needs to be defined as 0 to 13
bar absolute.
Table 16: Pressure sensor parameters
Symbolic name
o20 MinTransPres
o21 MaxTransPres
 NOTE:
BothDanfoss AKS 32R and Danfoss Saginomiya Pressure transmitter NSK-BExxx follows the relative (gauge) pressure,
therefore same rules apply as explained above in converting and defining it in bar absolute in EIM controller.
Temperature sensor Settings
The temperature sensor input is setup by default to accept PT1000 temperature sensor. The values for the sensor
can be adjusted to calibrate the sensor through the parameter "r09 Adjust S2".
Table 17: Temperature sensor value offset
Symbolic name
r09 Adjust S2
Valve Configuration
The EIM 365 can be configured to be used with a wide range of valves ETS 12.5 or 25; ETS 50; ETS 100; ETS 250; ETS
400; USER DEFINE; Saginomiya; ETS 6; CCMT; CCMT16; CCMT24; CCMT30; CCMT42; CTR; CCMT 0; CCMT 1; ETS Colibri
valve
Table 18: Valve configuration parameters
Symbolic name
EIM 365 common settings
n03 Valve type
User defined valves:
Only The EIM 365 can be configured to be used with to use a valve from a different manufacturer, then these
parameters must be provided by the user.
EIM
Applicable
© Danfoss | Climate Solutions | 2022.09
PNU
Description
Minimumtransducer pressure (in bar absolute x 10).
2034
Example: 0 bar absolute is entered as 0
Maximum transducer pressure(in bar absolute x 10).
2033
Example: 13 bar absolute is entered as 130
PNU
Description
S2 Offset adjustment to correct the sensor signal due
113
to long wires etc.
PNU
Description
0: ETS 12.5, ETS 25, KVS 15
1: ETS 50, CCM 10, CCM 20, CCM30
2: ETS 100, CCM 40
3: ETS 250, KVS 42
4 : ETS 400
5: User defined
6: UKV, SKV, VKV, PKV
7: ETS 6
8: CCMT 2, CCMT 4, CCMT 8
3002
9: CTM16
10: CCMT 24
11: CCMT 30
12: CMT 42
13: CTR
14: CCMT 0
15: CCMT 1
16: No valve selected
17: ETS 12C, 24C, 25C, 50C, 100C, KVS 2C, 3C, 5C
365
BC415322248492en-000101 | 18