Superheat controller, type EIM 365 (PV01)
Alarms and clearing alarms
Several alarms are registered and made available on modbus. Most of these are automatically cleared when the
error is no longer present. Sensor error : Temperature sensor error has a timeout of 10 minutes. This means that after
the reason for a sensor error has gone, the error will remain active for 10 minutes, and then it is cleared. for the
pressure sensor, the timeout is only 30 seconds.
There is an option to reset the errors externally by setting the 40075 (reset alarms) = 1.
Table 24: Related parameters
Symbolic name
---Reset alarm
--- EKC Error
---S2 Error
---S4 Error
---Pe inp.error
---No Rfg. Sel.
---LOC Alarm
--- CtrlStatus
© Danfoss | Climate Solutions | 2022.09
PNU
Description
2046
1= Clear alarm.
It is possible to clear alarms manually by setting Reset Alarms (40075). After set-
ting this, the alarm is keptactivefor
5seconds before being cleared.
20001
Common error flag. EKC Error is SET if any other Error Alarm is ON.EKC error is
auto cleared after the last active alarm has been cleared.
20002
S2sensor error. If the sensor error occurs, the valve OD will be set to 80% of the
Avg. opening (PNU 50021) - see.
S2alarm is auto cleared after 10 min after the alarm condition has been cleared.
20004
S4sensor error. If the sensor error occurs, the valve OD will be set to 80% of the
Avg. opening (PNU 50021) - see.
S4 alarm is auto cleared after 10 min after the alarm condition has been cleared.
20005
Pressure transmitter out of range. If the sensor error occurs, the valve OD will be
set to 80% of the Avg.opening(PNU 50021)
-see .
Pe alarm is auto cleared after 30 seconds.
20006
Refrigerantnot selected.
NoRefrigerant selected alarm is auto cleared immediately after setting the refrig-
erant.
50006
Loss of charge alarm. No action will be performed except setting the alarm.
3100
Bit mappped status register, see also Control status
BC415322248492en-000101 | 22