Table 13: Air Flow Performance - Side Duct Application
Supply Air Blower Performance (15 Ton) - Cooling Only 180 Mbh - Bottom Duct Connections
MOTOR
BLOWER
PULLEY
SPEED,
(TURNS
(RPM)
ESP
OPEN)*
(Pa)
3
HIGH STATIC DRIVE (m
/s)
1030
6.0
357
1070
5.0
405
1115
4.0
461
1155
3.0
514
1200
2.0
577
1240
1.0
636
MOTOR
BLOWER
PULLEY
SPEED,
(TURNS
(RPM)
ESP
OPEN)*
(iwg)
HIGH STATIC DRIVE (CFM)
1030
6.0
1.4
1070
5.0
1.6
1115
4.0
1.9
1155
3.0
2.1
1200
2.0
2.3
1240
1.0
2.6
NOTES: 1.Blower performance includes fixed outdoor air, 2" T/A filters, a dry evaporator coil and no electric heat.
2.Refer to Table 16 for additional static resistances.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static
High efficiency single package air conditioners and single package gas/electric units 6-1/2, 7-1/2, 8-1/2, 10 and 12-1/2 nominal tons 10.0-11.5 eer (48 pages)