York DCMF09NWM42Q1 Technical Manual

York DCMF09NWM42Q1 Technical Manual

Ductless single-split air conditioners and heat pumps

Advertisement

TECHNICAL
TECHNICAL
GUIDE
GUIDE
LX SERIES
DUCTLESS SINGLE-SPLIT
AIR CONDITIONERS AND HEAT PUMPS
16 SEER – 1 PHASE
3/4 THRU 2 NOMINAL TONS
MODELS: DCMF/DHMF
Due to continuous product improvement, specifications
are subject to change without notice.
Visit us on the web at
www.upgnet.com
Additional rating information can be found at
www.ahridirectory.org
WARRANTY SUMMARY*
Standard 2-Years limited parts warranty.
Standard 6-Years limited compressor warranty.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
DESCRIPTION
The Single-Split Series are ductless climate systems. They are
designed with a matching indoor unit for optimum performance and effi-
ciency. These climate systems are supported with accessories and doc-
uments to serve specific functions.
FEATURES
Variable Frequency Rotary Compressor - Twin rotary inverter compressor
on all models features high efficiency operation that modulates down to 15
Hz and as high as 120 Hz for reduced vibration and quiet operation. Brush-
less DC motor uses powerful Neodymium magnets that are approximately
15-20 times stronger than ferrite magnets used in conventional AC compres-
sors. The DC Inverter Control provides continuous operation, while adjusting
capacity according to room temperature. The accurate sensing of cooling or
heating loads prevents frequent changes in capacity and ensures efficient,
economical operation.
Low Ambient Cooling Operation Down to 5 °F - This feature allows for a
space to be air-conditioned even in outdoor temperatures as low as 5 °F.
This cooling ability is important when dealing with server equipment rooms,
surveillance mechanical rooms, restaurant kitchens, fitness centers, and
more.
Load Variation Management System - The outdoor coil thermistor continu-
ously monitors the temperature and communicates with the microprocessor.
Depending on the temperature measured, the compressor will be allowed to
increase the frequency if needed to meet the load or reduce frequency as
the load is reduced.
High Pressure Discharge Temperature - The compressor discharge line
thermistor continuously monitors the temperature and communicates with
the microprocessor. Depending on the temperature measured, the compres-
sor will be allowed to increase the frequency to meet the load or is forced to
run at the current or reduced frequency. If the temperature gets excessively
high, the compressor will be de-energized.
Defrost Control (Heat Pump Models) - Defrost cycle is automatically
enabled if there is a build-up of frost on the outdoor coil. Outdoor fan and
indoor blower operation is terminated during the defrost cycle. H1 is dis-
played on the indoor unit panel on the front cover during a defrost cycle.
Reversing Valve (Heat Pump Models) - 4-way interchange reversing valve
effects a rapid change in direction of refrigerant flow resulting in quick
changeover from cooling to heating and vice versa. Valve operates on sys-
tem pressure differential between outdoor unit and indoor unit.
R-410A Refrigerant - Unit is pre-charged with R410A refrigerant that uses
PVE refrigerant oil. Polyvinyl ether (PVE) is an innovative refrigerant oil spe-
cially formulated for hydrofluorocarbon (HFC) refrigeration systems. In addi-
tion to providing lubricating properties, it also has a number of other applied
advantages that help to increase the reliability of the refrigeration systems
where it is applied.
Refrigerant Line Connections, Service Valve - Outdoor units are designed
with easy service and maintenance in mind. Maintenance points are located
behind easy-access panels, to make installation and service a breeze for a
trained technician. Flare connection lines are located on side of unit cabinet.
Fully serviceable brass service valve prevents corrosion and provide access
to refrigerant system. Shut-off valve that can be fully shut off while 2-way
suction/vapor valve (with service port) may be front seated to manage refrig-
erant charge while servicing system.
Air Deflection Louvers - Horizontal louvers default to the cooling or heating
position when the unit is operating. Horizontal louvers can be set to a preset
oscillating range or fixed position from the wireless remote control. Full oscil-
lating is the default setting when button is pushed. Vertical louvers can be
manually adjusted to direct the airflow for optimal comfort.
Indoor Coil Freeze Protection - The indoor coil thermistor monitors the coil
temperature continuously. Any time the coil temperature drops below 30°F,
the compressor and the outdoor fan (30 seconds later) will be switched off
until the coil temperature rises above 43°F and the compressor has been off
for a minimum of 3 minutes.
I FEEL Function - When I FEEL is activated, the system will satisfy the cool-
ing or heating temperature setpoint where the remote control is located.
When I FEEL is deactivated, the system will satisfy the cooling or heating
temperature setpoint where the indoor unit is located. This feature provides
homeowners with optimum comfort whether they are near or far from the
indoor unit.
Hot Heat Pump (cold air prevention) - In heating mode, the indoor fan will
be delayed from 1 to 3 minutes to allow refrigerant to warm up and avoid
cold blow. This may occur during:
• Initial start-up of a heating cycle
• Immediately after completion of an Auto mode operation
• Heating under extremely low indoor temperatures
923178-UTG-B-0114

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DCMF09NWM42Q1 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for York DCMF09NWM42Q1

  • Page 1 923178-UTG-B-0114 DESCRIPTION TECHNICAL TECHNICAL The Single-Split Series are ductless climate systems. They are designed with a matching indoor unit for optimum performance and effi- ciency. These climate systems are supported with accessories and doc- GUIDE uments to serve specific functions. GUIDE FEATURES Variable Frequency Rotary Compressor - Twin rotary inverter compressor...
  • Page 2 923178-UTG-B-0114 Johnson Controls Unitary Products...
  • Page 3: Specifications

    923178-UTG-B-0114 SPECIFICATIONS AIR CONDITIONERS DCMF09NWM42Q1 DCMF12NWM42Q1 DCMF18NWM42Q1 DCMF24NWM42Q1 Model (Indoor/Outdoor) DCMF09CSM42Q1 DCMF12CSM42Q1 DCMF18CSM42Q1 DCMF24CSM42Q1 Function Cooling Cooling Cooling Cooling Rated Voltage 208/230 208/230 208/230 208/230 Frequency (Hz) 60Hz 60Hz 60Hz 60Hz Total Capacity (BTUH) (High/Standard/Low) 11500/9000/3800 12500/12000/3300 21000/18000/4500 24000/22000/6400 Total Capacity (W) (High/Standard/Low)
  • Page 4 923178-UTG-B-0114 AIR CONDITIONERS (Continued) Model of Outdoor Unit DCMF09CSM42Q1 DCMF12CSM42Q1 DCMF18CSM42Q1 DCMF24CSM42Q1 Compressor Manufacturer/trademark GREE GREE MITSUBISHI SANYO Compressor Type Inverter Rotary Inverter Rotary Inverter Rotary Inverter Rotary L.R.A. (A) 16.50 16.50 Compressor RLA (A) 6.22 6.22 10.86 11.38 Compressor Power Input (W) 1245 1630 Throttling Method...
  • Page 5 923178-UTG-B-0114 HEAT PUMPS DHMF09NWM42Q1 DHMF12NWM42Q1 DHMF18NWM42Q1 DHMF24NWM42Q1 Model (Indoor/Outdoor) DHMF09CSM42Q1 DHMF12CSM42Q1 DHMF18CSM42Q1 DHMF24CSM42Q1 Function Cooling Heating Cooling Heating Cooling Heating Cooling Heating Rated Voltage 208/230 208/230 208/230 208/230 Frequency (Hz) 60Hz 60Hz 60Hz 60Hz 11500/9000/ 11500/9000/ 12500/12000/ 12500/12000/ 21000/18000/ 23000/19200/ 24000/22000/ 26600/26600/ Total Capacity (Btu/h) (High/Standard/Low)
  • Page 6 923178-UTG-B-0114 HEAT PUMPS (Continued) Model of Outdoor Unit DHMF09CSM42Q1 DHMF12CSM42Q1 DHMF18CSM42Q1 DHMF24CSM42Q1 Compressor Manufacturer/trademark GREE GREE MITSUBISHI SANYO Compressor Type Inverter Rotary Inverter Rotary Inverter Rotary Inverter Rotary L.R.A. (A) 16.50 16.50 Compressor RLA(A) 6.22 6.22 10.86 11.38 Compressor Power Input (W) 1245 1630 Throttling Method...
  • Page 7 923178-UTG-B-0114 PRODUCT OPERATION CHARACTERISTIC CURVES 09K 12K Cooling Heating Condition Condition Indoor:DB 68°F F ° WB66.2°F Indoor air flow: Super High Indoor air flow: Super High Pipe length:24.6ft Pipe length:24.6ft Compressor Frequency(Hz) Compressor Frequency(Hz) Cooling Heating Condition Condition Indoor:DB 68°F F °...
  • Page 8 923178-UTG-B-0114 Cooling Heating Condition Condition Indoor:DB 68°F F ° WB66.2°F Indoor air flow: Super High Indoor air flow: Super High Pipe length:24.6ft Pipe length:24.6ft Compressor Frequency(Hz) Compressor Frequency(Hz) PRODUCT CAPACITY VARIATION RATIO 09K 12K Cooling Heating Condition Condition Indoor:DB 68°F Indoor:DB 80.6°F WB66.2°F Indoor air flow: Super High Indoor air flow: Super High...
  • Page 9: Operation Data

    923178-UTG-B-0114 OPERATION DATA Standard Heat Exchanger Temperature Condition (°F) Indoor Fan Outdoor Fan Compressor Pressure Pipe Temperature Model name Mode Mode Frequency (Hz) Indoor Outdoor P (MPa) T1 (°F) T2 (°F) COOLING 80/66.9 95/75 0.9 to 1.1 53.6 to 57.2 158 to 104 Super High High...
  • Page 10: Indoor Unit Dimensions

    923178-UTG-B-0114 PRODUCT CONSTUCTION VIEW & DIMENSIONS 09K 12K 21.6 21.3 27.0 Indoor Unit Dimensions Unit Gross Weight Model Size Air Conditioner Heat Pump 25 lbs (11.5 kg) 25 lbs (11.5 kg) 30.3 (770) 7.9 (201) 11.1 (282) 27 lbs (12 kg) 27 lbs (12 kg) 34.1 (866) 8.5 (216)
  • Page 11: Refrigerant System Diagram

    923178-UTG-B-0114 REFRIGERANT SYSTEM DIAGRAM 09K/12K/18K Cooling Only Models INDOOR UNIT OUTDOOR UNIT GAS SIDE 3-WAY VALVE Muffler Di s charge HEAT EXCHANGE (EVAPORATOR) Accumlator Suction COMPRESSOR HEAT EXCHANGE (CONDENSER) LIQUID SIDE 2-WAY VALVE Capillary Strainer COOLING See Page 12 for notes. 09K/12K/18K Heat Pumps INDOOR UNIT OUTDOOR UNIT...
  • Page 12: Indoor Unit

    923178-UTG-B-0114 24K Cooling Only Models INDOOR UNIT OUTDOOR UNIT GAS SIDE 3-WAY VALVE Muffler Di s charge HEAT EXCHANGE (EVAPORATOR) Suction Accumlator COMPRESSOR HEAT EXCHANGE (CONDENSER) LIQUID SIDE 2-WAY VALVE Electron expansion valve Strainer COOLING See below for notes. 24K Heat Pumps INDOOR UNIT OUTDOOR UNIT GAS SIDE...
  • Page 13: Wiring Diagram

    923178-UTG-B-0114 WIRING DIAGRAM Electrical Data Symbol Color Symbol Symbol Color Symbol Symbol Part Name INDOOR UNIT BlUE BROWN PROTECTIVE EARTH YELLOW GREEN BLACK YEGN YELLOW GREEN OUTDOOR UNIT Symbol Part Name Symbol Color Symbol Symbol Color Symbol CBB61 BROWN WHITE CBB65 BLUE YELLOW...
  • Page 14 923178-UTG-B-0114 09K & 12K Indoor Air Conditioners 18K & 24K Outdoor Air Conditioners Johnson Controls Unitary Products...
  • Page 15 923178-UTG-B-0114 18K & 24K Indoor Air Conditioners 09K & 12K Outdoor Heat Pumps Johnson Controls Unitary Products...
  • Page 16 923178-UTG-B-0114 09K & 12K Indoor Heat Pumps 18K & 24K Outdoor Heat Pumps Johnson Controls Unitary Products...
  • Page 17: Description Of Each Control Operation

    923178-UTG-B-0114 18K & 24K Indoor Heat Pumps DESCRIPTION OF EACH CONTROL OPERATION Start cooling amb. Temperature & Current Parameters preset Original working state • Indoor preset temperature (T preset +3.6 ºF preset Stop cooling • Indoor ambient temperature (T 6 minutes 3 minutes 6 minutes •...
  • Page 18: Fan Mode

    923178-UTG-B-0114 Dehumidification Mode h. After 60 seconds, the compressor and the outdoor unit fan will start running. The indoor fan will run under preset cold 1. Dehumidification Mode Operation air prevention conditions. H1 will be displayed on the • When T >...
  • Page 19 923178-UTG-B-0114  When T ≥ 144⁰F, compressor is de-energized and • When T +3.6°F< T < T +41°F, the system con- preset amb. preset tube tinues to run normally the indoor fan will continue to run for about 30 seconds and stops.
  • Page 20 923178-UTG-B-0114 RESISTANCE TABLES Resistance Table of Ambient Temperature Sensor for Indoor and Outdoor Units (15K) Temp. (°F) Resistance (k) Temp. (°F) Resistance (k) Temp. (°F) Resistance (k) Temp. (°F) Resistance (k) -2.2 138.1 18.75 138.2 3.848 208.4 1.071 -0.4 128.6 69.8 17.93 3.711...
  • Page 21 923178-UTG-B-0114 Resistance Table of Outdoor and Indoor Tube Temperature Sensors (20K) Temp. (°F) Resistance (k) Temp. (°F) Resistance (k) Temp. (°F) Resistance (k) Temp. (°F) Resistance (k) -2.2 181.4 25.01 138.2 5.13 208.4 1.427 -0.4 171.4 69.8 23.9 4.948 210.2 1.386 162.1 71.6...
  • Page 22 923178-UTG-B-0114 Resistance Table of Outdoor Discharge Temperature Sensor (50K) Temp. (°F) Resistance (k) Temp. (°F) Resistance (k) Temp. (°F) Resistance (k) Temp. (°F) Resistance (k) -20.2 853.5 120.2 18.34 190.4 4.754 -18.4 799.8 51.8 93.42 17.65 192.2 4.609 -16.6 53.6 89.07 123.8 16.99...
  • Page 23: Removal Procedure Of Indoor Unit

    923178-UTG-B-0114 REMOVAL PROCEDURE Removal Procedure of Indoor Unit Be sure to wait for a minimum of 10 minutes after turning off all power supplies before disassembly. STEPS PROCEDURES Axonometric drawing for the complete unit. 1. Before disassembly of the unit panel a.
  • Page 24 923178-UTG-B-0114 STEPS PROCEDURES Clasp Pull the clasps at both sides slightly, and then remove the panel. 4. Remove panel Panel Remove the axial bush on the horizontal louver, and then 5. Remove horizontal louver remove the horizontal louver. horizontal louver a.
  • Page 25 923178-UTG-B-0114 STEPS PROCEDURES Screw Cap a. Remove the screw caps on front case. Screw b. Remove screws connecting the front case. 7. Remove front case Front Case c. Remove the front case. Remove earthing screws, and screw 8. Remove earthing wire then remove the earthing wire.
  • Page 26 923178-UTG-B-0114 STEPS PROCEDURES 10. Remove temperature sensor Pull out the indoor temperature sensor. temperature sensor a. Pull out 6 sockets on PCB board. 11. Remove electric box Screw b. Pull out two screws on electric box. Electric c. Remove the electric box. Water Tray Pull the water tray upwards, 12.
  • Page 27 923178-UTG-B-0114 STEPS PROCEDURES Remove two screws on pipe-stopping plate for indoor unit, and then remove 14. Remove pipe-stopping plate the pipe-stopping Screw Pipe-Stopping Plate Screw Damping Board Remove 2 screws on damping board, and then 15. Remove damping board remove the damping board. Screw a.
  • Page 28 923178-UTG-B-0114 STEPS PROCEDURES Blade Motor a. Remove screws fixing cross flow blade and motor. 18. Remove cross flow blade and motor b. Remove the motor sub-assy. c. Separate two cross flow blade. a. Remove the cushion rubber on cross flow blade. Cushion Rubber 19.
  • Page 29: Removal Procedure Of Outdoor Unit

    923178-UTG-B-0114 Removal Procedure of Outdoor Unit Be sure to wait for a minimum of 10 minutes after turning off all power supplies before disassembly. STEPS PROCEDURES Top Panel a. Use the screwdriver to remove the screws connecting the top panel and panel and side panels. Remove the top panel.
  • Page 30 923178-UTG-B-0114 STEPS PROCEDURES Guard Grille Twist off the screws fixing the guard grille and then remove the guard grille. 4. Remove guard grille Twist off the screws fixing the handle and then remove the handle. 5. Remove handle Handle Right Side Plate Twist off the screws connecting the right side plate and chassis, valve support and...
  • Page 31 923178-UTG-B-0114 STEPS PROCEDURES Electric Box b. Twist off the screws on electric box, cut off the tieline with scissors or pliers, pull out the wiring terminal, pull it upwards to remove the electric box. 7. Remove electric box (Continued) Electric Box 1 c.
  • Page 32 923178-UTG-B-0114 STEPS PROCEDURES a. Twist off the tapping screws fixing the motor, pull out the pin of leading wire for motor and then remove the motor. Motor 10. Remove motor and motor support Motor Support b. Twist off the tapping screws fixing the motor support, pull it upwards and then remove the motor support.
  • Page 33 923178-UTG-B-0114 STEPS PROCEDURES Twist off the 3 foot nuts on compressor and then remove the compressor. 13. Remove compressor Compressor Twist off the screws connecting isolation sheet and end plate of condenser and chassis, and then 14. Remove isolation sheet Isolation remove the isolation sheet.
  • Page 34 S1-52642443015 LINESET,MINISPLIT,3/8LX7/8SX15',3/8(M8) S1-230-EB3 ELBOW,INSIDE,90DEG,SPEEDICHANNEL,3"(M10) S1-52642443025 LINESET,MINISPLIT,3/8LX7/8SX25',3/8INS S1-230-EB4 ELBOW,INSIDE,90DEG,SPEEDICHANNEL,4"(M10) S1-230-EB6 ELBOW,INSIDE,90DEG,SPEEDICHANNEL,6"(M10) Subject to change without notice. Published in U.S.A. 923178-UTG-B-0114 Copyright © 2014 by Johnson Controls, Inc. All rights reserved. Supersedes: 923178-UTG-A-1112 York International Corp. 5005 York Drive Norman, OK 73069...