Download Print this page

Maple Systems IO-SA0400 User Manual

Rtd & tc modules

Advertisement

Quick Links

USER MANUAL
MAPLE MODULAR PLC
RTD & TC Modules
IO-SA0400
IO-SA0400T
- 1 -

Advertisement

loading

Summary of Contents for Maple Systems IO-SA0400

  • Page 1 USER MANUAL MAPLE MODULAR PLC RTD & TC Modules IO-SA0400 • IO-SA0400T • - 1 -...
  • Page 2: Table Of Contents

    Contents General Specifications ........8 Performance Specifications ......9 Features ............11 Wiring ............13 Appearance & Dimensions ......14 Product Warranty .......... 16 - 2 -...
  • Page 3 Reproduction of contents, in whole or part of this manual, without written permission from MAPLE SYSTEMS Inc. is prohibited. Safety symbols are classified into two categories: “WARNING” and “CAUTION”. Warning This symbol describes situations that could cause major or fatal injury to the user.
  • Page 4 Design Precautions ( Warning) Please install a safety circuit to protect the entire control system in case of an unexpected power shut-down or PLC module malfunction. Such anomalies may severely compromise the integrity of the overall system. External to the PLC, please install circuits and switches to safeguard the system from mechanical damages (ex.
  • Page 5 Precautions for mounting ( Caution) Use the PLC in an environment that meets the general specifications given in this manual. Using this PLC in any environment outside the range of the general specifications could result in electric shock, fire, malfunction, or damage to or deterioration of the product. Please ensure that each module is installed correctly in its place.
  • Page 6 Precautions for wiring of RTD & TC Module ( Caution) Cables for module input signals should be separate from AC power to prevent the influence of surge or induction noise occurring from AC. Select a cable considering the ambient temperature and allowable current. AWG16-28 is recommended.
  • Page 7 Precautions for test run and repair ( Caution) Do not dissociate the PCB from the module’s casing or make any modifications to the device. Doing so may cause fire, electric shock or malfunction. When mounting or separating the module, make sure to turn off power to the PLC and all other devices.
  • Page 8: General Specifications

    General Specifications Items Specification Standards Ambient -10℃–65℃ Temp. Storage -25℃–80℃ Temp. Ambient 5–95% RH, Non-condensing Humidity Storage 5–95% RH, Non-condensing Humidity For discontinuous vibration Frequency Acceleration Amplitude Times 5 ≤ f < 9 Hz 3.5 mm 10 times in X, Y, Z 9 ≤...
  • Page 9: Performance Specifications

    Performance Specifications (IO-SA0400) Items Specification PT100, JPT100, PT1000, RTD Type Ni1000 (DIN43760), Ni1000 (TCR5000) PT100: -200.0–600°C (18.52–313.71 Ω) JPT100: -200.0–600°C (17.14–317.31 Ω) Range of Temperature Input PT1000:-200.0– 600°C (185.2–3137.1 Ω) Ni1000 (DIN 43760): -50.0–160°C (742.6–2065.9 Ω) Ni1000 (TCR5000):-50.0–160°C(790.9–1863.6 Ω) -192...
  • Page 10 Performance Specification (IO-SA0400T) Items Specification Thermocouple Type K, J, E, T, B, R, S, N type Digitally converted value: 0–16000 (-8000–8000)/ - 192–16191 (-8192–8191) Digital Conversion Converted temperature value: Range of measured temperature (one digit after the decimal point * 10) Range of measured Range of measured Thermocouple...
  • Page 11: Features

    Features of RTD Module (IO-SA0400) RTD conversion module converts temperatures of PT100, JPT100, PT1000, NI1000 into (℃, °F) or 14-bit (or 16-bit) digital value. 1) Used to convert temperature from PT100, JPT100, PT1000, or Ni1000 into a decimal value (℃, °F) with one decimal place of accuracy. It can output a digital value in the range of -192–16191 (0–65000), -8192–8191 (-32768–32767), 0–16000 (0–64000),...
  • Page 12 Features of TC Module (IO-SA0400T) TC is the conversion module that measures temperature from a thermocouple (K, J, E, T, B, R, S, N) and converts temperatures into (℃, °F), or a 14-bit digital value. 1) Can show minimum -200℃ and maximum +1200℃ temperature value, or digital value -192–16191 (-8192–8191).
  • Page 13: Wiring

    Wiring of RTD (IO-SA0400) Channel A Terminal B Terminal b Terminal CH 1 Terminal 1 Terminal 2 Terminal 3 CH 2 Terminal 4 Terminal 5 Terminal 6 CH 3 Terminal 7 Terminal 8 Terminal 9 CH 4 Terminal 10 Terminal 11...
  • Page 14: Appearance & Dimensions

    Appearance IO-SA0400 IO-SA0400T - 14 -...
  • Page 15 Dimensions ► Both IO-SA0400 and IO-SA0400T have the same dimensions. (Unit: mm) - 15 -...
  • Page 16: Product Warranty

    Product Warranty Warranty Statements are included with each unit at the time of purchase and are available at www.maplesystems.com. - 16 -...
  • Page 17 MEMO...
  • Page 18 MEMO...
  • Page 19 MEMO...
  • Page 20 808 134th St SW #120 Everett, WA 98204 Phone +1 425-745-3229 Web: www.maplesystems.com...

This manual is also suitable for:

Io-sa0400t